InteliLite 9 Global Guide
146
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
Yes
Step
1 kW
Comm object
8276
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal power of the gen-set. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note:
To lock this setpoint against editing you also have to lock setpoint
,
and
Nominal Power
Subgroup: Current settings
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
8275
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
It is current limit for mains current protections and means maximal continuous mains current. Nominal
Current can be different from mains rated current value.
Note:
To lock this setpoint against editing you also have to lock setpoint
,
and
Nominal Current