InteliLite 4 MRS16 Operator Guide
18
3.1 User access management alarms
The controller comes to the customer with turned on Production mode, the default administrator password and
with no filled email address for password reset. Due to the security reasons following user access management
alarms appear. Detailed description of situation when the alarms are active are described below:
Wrn Production Mode
is present in the alarm list all the time while production mode is turned on. To turn
off the Production mode go to User management and uncheck the checkbox Production mode or go to
Production Mode display screen and select disable.
Wrn Default Password
appears in alarmlist when the default administrator password is set and
communication module is plugged in the controller. The purpose of alarm is to inform that the controller might
be or is connected to the untrusted interface and cybersecurity rules are not fulfilled due to default
administrator password.
Wrn Password reset e-mail addr is not set
appears in alarmlist when there is no email address set and
the administrator password is not the default one. The purpose of alarm is to inform that there is possibility
that the controller might not be accessible by administrator password due to forgotten password reason.
Password reset procedure cannot be performed without filled email address. To fill out email address, the
administrator password is required.