InteliLite4 AMF20 Global Guide
494
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
48
Description
The output is intended for control of undervoltage coil of mainsbus circuit breaker. The output is active the
whole time when the controller is switched on. The output is deactivated for at least 5 seconds in the
moment the breaker has to be switched off.
Image 8.51 MCB UV Coil close command
Image 8.52 MCB UV Coil open command
MCB UV Coil