InteliLite4 AMF20 Global Guide
466
LBO: A
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
1247
Description
This output is activated together with binary output
and opens after the engine is
stopped or in case that engine is not ready.
Image 8.30 Air Valves
Air Valves
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
9
Description
Output is activated when any BOC alarm appears.
The output opens, if:
No BOC alarm is active and
Fault reset
button is pressed
AL Common BOC
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
6
Description
Output is activated when any sensor fail alarm appears.
The output opens, if:
No sensor fail alarm is active and
Fault reset
button is pressed
AL Common Fls