InteliLite4 AMF20 Global Guide
258
Maintenance Timer 2 Interval
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
1 .. 36 [month] / Disabled
Default value
Disabled
Alternative config
NO
Step
1 month
Comm object
20584
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer counts down all the time, setting is done in months, but actual
value is displayed and counted in days. If it reaches zero, an alarm appears, but the
timer still counts down to negative values. When the value 37 (Disabled) is set, then the maintenance
function is disabled and counter does not count and the counter value disappears from controllers
statistics.
Reset of the timer can be done by adjusting this setpoint again. Setting of the setpoint does not change
when the reset is done, only the
Maintenance Timer 2 Interval (page 413)
value changes to reflect reset
of the maintenance timer.
Maintenance Timer 2 Protection
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
Warning / BOC [-]
Default value
Warning
Alternative config
NO
Step
[-]
Comm object
20587
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Type of the maintenance alarm of both
Maintenance Timer 2 RunHours (page 257)
and
.