InteliLite4 AMF20 Global Guide
257
Maintenance Timer 1 Protection
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
Warning / BOC [-]
Default value
Warning
Alternative config
NO
Step
[-]
Comm object
20586
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Type of the maintenance alarm of both
Maintenance Timer 1 RunHours (page 256)
and
.
Subgroup: Maintenance Timer 2
Maintenance Timer 2 RunHours
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
0 ... 9 999 [h] / Disabled
Default value
Disabled
Alternative config
NO
Step
1 h
Comm object
13854
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer counts down when engine is running. If it reaches zero, an alarm appears, but the timer
still counts down to negative values. When the value 10 000 (Disabled) is set, the Maintenance function is
disabled and the counter value disappears from controllers statistics.
Reset of the timer can be done by adjusting this setpoint again.