InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
60
The alarm CoolDown Cd, red color). Its configurable type of alarm, where isn’t necessary immediately
to stop the engine. E.g. because of low fuel level can be the engine switched by degrees over cooling
time and idle speed.
Apart from here above mentioned “ready to wear” basic protections, the user can configure each
analog or binary input as a protection. The configuration of binary inputs is done in LiteEdit, in the
window Modify.
H
INT
Class B protection: for binary inputs configured as a protection, the individual delay can be set by the
means of setpoints BIN1 Prot Del, BIN2 Prot Del, etc.
The configuration of the analog inputs can be done by a similar way, in LiteEdit, in the window Modify
and in the group of setpoints Engine protect, where is possible to set the alarm levels by means of
setpoints.
H
INT
Class C protection: the analog inputs AIN4, AIN5, AIN6
and AIN7 behave either “normally“ or
according to the class C definition according to the SP AINx Eval.
C
AUTION
!
The LBI Prot Test blocks temporarily all the protections in order to perform tests etc.
H
INT
For other details about the protections, see the paragraphe Setpoints, Engine protect.
6.8 Engine RPM control in MAN mode
There are following options to setup and change the engine speed:
Start to Nominal RPM and run at constant speed.
Start to Idle speed and Automatically (Idle time) or manually by Binary input: Nominal/Idle
ramp to Nominal (or preset) RPM.
Switch the RPM in three steps by Binary inputs BI Speed Sel1, 2, 3.
Ramp engine RPM Up/Down by Binary inputs BI Speed Up and Speed Down.
Control engine RPM by Analog input - e.g. by potentiometer.