InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
58
State
Condition of the transition
Action
Next state
BI: Nominal/Idle
is active
FUEL
SOLENOID
on
STOP SOLENOID
off
READY TO LOAD
off
Running
RPM = 0 or any other shutdown
condition
FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
Shutdown
Cooling
Cooling time
elapsed
FUEL SOLENOID off
STOP SOLENOID on
Stop
RPM = 0 or any other shutdown
condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Start request
READY TO LOAD on
Running
Stop
RPM = 0,
Oil pressure not detected, D+
not active
Ready
60 sec.
Elapsed
Stop (Stop fail)
1
The start-up sequence can be interrupted in any time by coming stop request
2
Fuel solenoid is switched on with advance of 1s fixed before starter motor is switched on.
H
INT
Threshold level for D+ input is 80% supply voltage; activation delay is 1s (to override short firings
during cranking
– for example in cold conditions).
Speed request:
Engine speed is constant or set manually using
Engine params
setpoints and Binary inputs.
6.4 AUT mode
The controller does not respond to START, STOP buttons. Engine start/stop request is given by
binary input REM START/STOP.
Engine speed request is sourced from PI loop (see below function 3) in AUT mode.
PI loop and Hysteresis comparator functions can be used both for Engine Load Limitation or any other
control function.
Speed request:
Engine speed is adjusted automatically by internal PID loops (when active) -
Regulator
setpoints
group.
6.5 Engine without pickup operation
The RPM pickup input is ignored when
Engine params
:
Gear teeth
= 0. The engine running state is
then detected based on
Engine params
:
Starting POil
or
Engine params
:
D+ function
= ENABLED.
Starting Poil
signal can be analog or binary. Even the binary signal is to be connected to AIN1 input. In
LiteEdit, window
Modify
, input
Oil Pressure
, check off the option
Binary
. The setpoint
Starting Poil
set
to 1.