4.1.5 Binary output protections
Do not connect binary outputs directly to DC relays without protection diodes, even if they are not
connected directly to controller outputs.
4.1.6 Magnetic pick-up
To ensure proper function:
Use a shielded cable
Be aware of interference signal from Speed governor, if one speed pick up is used.
If engine will not start:
Check ground connection from pick-up to controllers, eventually disconnect ground connection
to one of them
Galvanic separate InteliDrive Lite RPM input using ComAp separation transformer RPM-ISO
(1:1)
Use separate pick-up for Speed governor and InteliDrive Lite