InteliDrive DCU Marine - 3.0.0 Global Guide
119
Setpoint group
Comms Settings
Related FW
3.0.0
Range [units]
[DISABLED, ENABLED]
Default value
DISABLED
Step
[-]
Comm object
11327
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
The setpoint enables/disables logging of remote communication activity. If logging is enabled connection
and disconnection of each remote terminal as well as entering access code are recorded into the history.
Note:
The terminal is disconnected automatically after 5 min of inactivity and next communication
request from the same terminal is considered as a new connection. When logging is enabled in certain
conditions the history may be filled up with large number of records related to the communication and
important records may be overwritten quite fast.
LB/UART Log
Setpoint group
Comms Settings
Related FW
3.0.0
Range [units]
[9600, 19200, 38400, 57600, 115200] [bps]
Default value
9600
Step
[-]
Comm object
24477
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
The setpoint adjusts communication speed of the RS232 interface when
is set to
MODBUS.
RS232 MBCSpd
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...