InteliDrive DCU Industrial 3.4.0 Global Guide
331
Analog inputs (not electric separated)
8, no galvanic separated
Measuring
±100 mV
Accuracy
± 0.1 % of actual value + ± 100 µV (± 3 °C)
Internal sensor for measuring cold junction - Accuracy
±1 °C in temperature range -20 °C ÷ +70 °C
Galvanic separation
CANbus is galvanic separated from the
measurement and power supply.
All analog inputs are galvanic separated from
power supply.
Analog inputs are not galvanic separated
between channels
Power supply
8 to 36 V DC
Protection
IP20
Current consumption
35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature
- 40 °C to + 80 °C
Operating temperature
- 30 °C to + 70 °C
Heat radiation
2 W
8.2.8 IGS-PTM
Description
IGS-PTM is modification of standard IG-IOM module with four analog inputs, which can be configured for range: