Warning
Indication only (no engine stop)
Shutdown
Fast engine stop
Cooldown
Engine stop with cooling period
Fail sensor
Measured value is out of sensor characteristics.
BW
Indi Broken wire detection
SBW
Shut down + Broken wire detection
W Fls
Warning is activated in the case of sensor fail as well
Sh Fls
Shut down is activated in the case of sensor fail as well
Sd override
This protection stays active in the case of Sd override is activated.
Alarm only
Only Alarm list indication, disappear without confirmation
HistRecOnly
History record only
Protection types
8.1.5 Values
What values are:
Values (or quantities) are analog or binary data objects, measured or computed by the controller, that are
intended for reading from the controller screen, PC, MODBUS, etc. Values are organized into groups according
to their meaning.
List of value groups
For full list of values go to the chapter