InteliDrive DCU Industrial 3.4.0 Global Guide
276
Statistics
Value group
Statistics
Related FW
3.4.0
Resolution [units]
1 [h]
Comm object
8206
Related applications
AS, SS
Description
Engine running hours value.
RunHours
Value group
Statistics
Related FW
3.4.0
Resolution [units]
1 [-]
Comm object
8207
Related applications
AS, SS
Description
Successful engine start number counter. The counter is increased by 1 even if the particular start command
will take more than one attempt.
Note:
The counter can be readjusted / reset from InteliMonitor menu Monitor -> Set statistics.
NumSuccStarts
Value group
Statistics
Related FW
3.4.0
Resolution [units]
1 [-]
Comm object
10149
Related applications
AS, SS
Description
Unsuccessful starts counter. The counter is incremented always when Start fail alarm is issued.
Note:
The counter can be readjusted / reset from InteliMonitor menu Monitor -> Set statistics.
NumUnscStarts
Value group
Statistics
Related FW
3.4.0
Resolution [units]
1 [-]
Comm object
9648
Related applications
AS, SS
Description
This is maintenance countdown timer. The timer is located in setpoints group
Engine protect
as well as in
Statistics values. Adjust the timer to the requested maintenance interval. It will be decremented while the
engine is running. The alarm WrnServiceTime is issued as soon as the timer counts down to zero.
Service Time
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...