InteliDrive DCU Industrial 3.4.0 Global Guide
123
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
50.0
Force value
Alternative config
Step
0.1 % of Requested RPM range.
Comm object
10008
Related applications
AS
Description
When
is closed the
opens (this action deactivates
loadsharing mode if it was activated before) and
is set to
Engine params:
FireAlarmSpeed
value.
FireAlarmSpeed
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
[ENABLED, DISABLED]
Default value
DISABLED
Force value
Alternative config
Step
[-]
Comm object
10098
Related applications
AS, SS
Description
ENABLED:
is defined by
setpoint that can be
modified by Fast edit function from front panel (4 sec Enter, / ¯, Enter).
DISABLED:
t is changed via
/
or via
, see
t charts for
and
modes.
EnLocalSpeed
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
0.0
Force value
Alternative config
Step
0.1
Comm object
9948
Related applications
AS, SS
Description
Setpoint specifies
when
= ENABLED. Setpoint
can be changed as standard setpoint or by Fast edit function: press Enter for 4 sec, / ¯ set value, press
Enter to confirm, see
charts for PRP and AUX / EME / HRB modes.
Local Speed
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...