InteliCharger 500,
©ComAp –June 2012
4
ICHG-500 - Reference Guide.pdf
5 INSTRUMENTATION
Charger Fail
Alarm LED indicator on front panel, Green = healthy / Red = failed.
Fault Alarm
LED indicator on front panel, Green = healthy / Red = failed.
Volt free form C contact set, de-energising on fault. The charger failed
alarm must be active for 60 seconds to de-energise the fault signal.
6 CHARGING PROFILE
3 stage bulk / absorb / float modes. The charger will automatically switch to bulk (auto-boost) mode on
a low battery condition. Once the bulk voltage level is reached the charger will switch to absorb (boost
run-on) mode. The absorb time period is variable and dependent on the length of the bulk charging
period. On expiration the charger switches back to float mode.
7 COOLING
Convection cooled, bottom to top air-flow is required.
8 TERMINATION
AC Input
Maximum cable size = 4.0 Sq.mm.
Terminal designations:
LIN Line
NIN Neutral
EIN Earth
DC Output (Battery)
Maximum cable size = 4.0 Sq.mm.
Terminal designations:
B+OUT BVe
B-OUT Battery
–Ve
Manual Boost
Maximum cable size = 2.5 Sq.mm.
Terminal designations:
21 Link to enable
22
Remote Fault Signal
Maximum cable size = 2.5 Sq.mm.
(Volt free form C)
Terminal designations:
18 Normally Closed
19 Common
20 Normally Open