2  EQUIPMENT RATING 

Input Voltage    

 

Switchable 90-132 Vac or 180-264Vac 1 Ph. 47-63 Hz. 

 
Inrush Current    

 

45A worst case. 

 
Maximum Input Current  

8A @ 115Vac 3.2A @ 230Vac. 

 
Output Voltage   

 

24Vdc Nominal 
Works preset to 27.5V float / 28.8V boost. 

Output voltage can be adjusted but a re-calibration MUST be 
performed (see section 9 of this specification). 
 

Output Current   

 

20A works preset. 

 
Recommended   

 

Flooded Lead Acid. 

Battery Types   

 

Sealed AGM (Sealed Lead Acid). 
Gel. 
Ni-Cad. 
 
Please contact us for other battery types. 

 
Fault Contact    

 

1A 30V DC 

3  ENVIRONMENT 

Working Temp. Range   

-20 to +50 C. 

 
Storage Temp. Range    

-40 to +85 C. 

 
Working Humidity  

 

20-90% non-condensing RH. 

4  PROTECTION 

 
AC Input  

 

 

Internal fast blow fuse. 
Upstream input fuse should be fitted. 
 

DC Output 

 

 

 ATO blade type fuse 25A 32Vdc. 

 
Short Circuit / Overload  

Constant current limiting with automatic recovery. 
Over Temperature Unit will shut-down if internal temperatures are 
exceeded. Automatically switches back on once the unit has cooled. 
 

Over Voltage    

 

Output voltage shut-down. Recycle AC input power to reset. 

 
Reverse Battery 

 

Internal diode (will blow DC output fuse). 

 
 
 

Summary of Contents for InteliCharger 500

Page 1: ...F CONTENTS 1 Document information 2 2 EQUIPMENT RATING 3 3 ENVIRONMENT 3 4 PROTECTION 3 5 INSTRUMENTATION 4 6 CHARGING PROFILE 4 7 COOLING 4 8 TERMINATION 4 9 CONNECTION 5 10 APPENDIX A Automatic Calibration Routine 5 11 APPENDIX B Manual Calibration Routine 6 12 APPENDIX C DEFAULT FACTORY 6 InteliCharger InteliCharger 500 24V 20A Intelligent Automatic Battery Charger September 2012 ...

Page 2: ...ment information INTELICHARGER 500 REFERENCE GUIDE WRITTEN BY ALES PETRIK 2012 COMAP LTD KUNDRATKA 17 PRAHA 8 CZECH REPUBLIC PHONE 420246012111 FAX 420266316647 WEB HTTP WWW COMAP CZ E MAIL INFO COMAP CZ DOCUMENT HISTORY REVISION NUMBER RELATED SW VERSION DATE r1 1 9 2012 ...

Page 3: ... Sealed AGM Sealed Lead Acid Gel Ni Cad Please contact us for other battery types Fault Contact 1A 30V DC 3 ENVIRONMENT Working Temp Range 20 to 50 C Storage Temp Range 40 to 85 C Working Humidity 20 90 non condensing RH 4 PROTECTION AC Input Internal fast blow fuse Upstream input fuse should be fitted DC Output ATO blade type fuse 25A 32Vdc Short Circuit Overload Constant current limiting with au...

Page 4: ...lk voltage level is reached the charger will switch to absorb boost run on mode The absorb time period is variable and dependent on the length of the bulk charging period On expiration the charger switches back to float mode 7 COOLING Convection cooled bottom to top air flow is required 8 TERMINATION AC Input Maximum cable size 4 0 Sq mm Terminal designations LIN Line NIN Neutral EIN Earth DC Outp...

Page 5: ...charge the output current will reduce High output current discharged battery low output current charged battery When the battery has fully charged its voltage can be checked with a DVM across the battery terminals NOTE If the float voltage is adjusted from factory default then the alarm system MUST be re calibrated following the instructions below 10 APPENDIX A Automatic Calibration Routine NOTE T...

Page 6: ...reen Set Boost off Voltage high level operate PROG push button Red Green Set Boost off Reset Voltage low level operate PROG push button Red Red Set Charger Fail Low Voltage Alarm operate PROG push button Green Red Set Charger Fail Low Voltage Reset operate PROG push button Red Red Set Charger Fail High Voltage Alarm operate PROG push button Green Red Set Charger Fail High Voltage Reset operate PRO...

Page 7: ...InteliCharger 500 ComAp June 2012 7 ICHG 500 Reference Guide pdf ...

Reviews: