IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
194
setpoint
N
OTE
:
See encoding table in the description of the input
Binary input: Priority sw C
Related FW
3.0
Description
and
that can be used for selection of the power management priority externally.
These inputs are optional and if not configured, the priority is then adjusted by the
setpoint
N
OTE
:
See encoding table in the description of the input
Binary input: Priority sw D
Related FW
3.0
Description
and
that can be used for selection of the power management priority externally.
These inputs are optional and if not configured, the priority is then adjusted by the
setpoint
N
OTE
:
See encoding table in the description of the input
Binary input: GroupLink
Related FW
3.0
Description
This input is used for logical connection and disconnection of the two gen-set
groups selected by setpoints
and
. If the input is
active, then the two selected groups will perform power management, kW-sharing
and kVAr-sharing together as one large group.
For linking of one couple of groups use this input only at one controller, e.g. the
nearest to the bus tie breaker which physically disconnects the groups, and
connect the input to the BTB feedback contact.
N
OTE
:
This function is independent on the group which the particular controller belongs
to, i.e. the controller can provide linking function e.g. for groups 3,4 although it self
belongs to group 2.
Binary input: PulseCounter 1
Related FW
3.0
Description
This is the input of the
PulseCounter #1
module. The module counts pulses at the
input and if the input pulses counter reaches value given by the setpoint
, the counter value
Statistic
) is