IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
82
#1) backlight is switched off.
N
OTE
:
When IntelliVision is used this setpoint does not adjust its behavior. Its backlight is
adjusted by internal IntelliVision "setpoint".
OFF
The backlight is off all the time
NO
TIMEOUT
The backlight is on all the time
Setpoint: DispBklStrtOff
Group
Basic settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
If this setpoint is in ENABLED position the display backlight is temporarily
switched off during gen-set start.
Setpoint: ConvCoefPulse1
Group
Engine Params
Range [units]
1 .. 6500 [-]
Related FW
3.0
Description
This setpoint adjusts the rate of increasing of the PulseCounter #1 module. The
module counts pulses at the input
and if the input pulses counter
reaches value given by this setpoint, the counter value
PulseCounter 1
(in the
group Statistic) is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Setpoint: ConvCoefPulse2
Group
Basic settings
Range [units]
1 .. 6500 [-]
Related FW
3.0
Description
This setpoint adjusts the rate of increasing of the PulseCounter #2 module. The
module counts pulses at the input
and if the input pulses counter
reaches value given by this setpoint, the counter value
PulseCounter 2
(in the
group Statistic) is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Setpoint: ConvCoefPulse3
Group
Basic settings