IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
191
Binary input: Load res 3
Related FW
3.0
Description
This input is used to activate the
load reserve set #3
instead of the set #1, which
is active by default. The set #3 is adjusted by setpoints:
•
switched to absolute (kW-based) mode
•
and
switched to relative (%Pnom-based) mode.
C
AUTION
!
All controllers cooperating together in Power management must have
the same
load reserve set selected.
N
OTE
:
It is possible to use
virtual peripheries
for distribution of the binary signal from one
physical switch connected to one controller to all other controllers over the CAN
bus. See example in the description of the input
Binary input: Load res 4
Related FW
3.0
Description
This input is used to activate the
load reserve set #4
instead of the set #1, which
is active by default. The set #4 is adjusted by setpoints:
•
switched to absolute (kW-based) mode
•
and
switched to relative (%Pnom-based) mode.
C
AUTION
!
All controllers cooperating together in Power management must have
the same
load reserve set selected.
N
OTE
:
It is possible to use
virtual peripheries
for distribution of the binary signal from one
physical switch connected to one controller to all other controllers over the CAN
bus. See example in the description of the input
Binary input: MinRun power 1
Related FW
3.0
Description
This input is used to activate the function Minimal running power #1, which is
adjusted by setpoint
N
OTE
:
The default value of minimal running power, which takes place while none of the
inputs
MinRun power x
, is 0kW.
N
OTE
:
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).