ID-FLX Lite & Telecom Global Guide
138
Comm object
8260
Related applications
Description
Limit for Warning Underspeed protection. Active protection is indicated as “Wrn Underspeed” in Alarm list.
Under speed Warning protection is inactive 5 s after RPM is over
and during the
Idle time.
The
is deactivated when Wrn underspeed protection is active and needs the
Fault reset for activation after RPM is over Underspeed limit.
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
5
-
Step
1
Comm object
12620
Related applications
Description
Engine is switched to Cooling state when Binary input FlowSwitch is not closed within Flow SwitchDel after
„Running“ (Ready to load) engine state activation.
Flow SwitchDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
DISABLED, ENABLED [-]
Default value
-
Step
-
UnderspeedSd