Columbia MCB-100J Installation, Operation & Maintenance Manual Download Page 18

18

12 - NORMAL SEQUENCE OF OPERATION

13 - GENERAL INSTRUCTIONS

Thermostat actuates on call for heat, 

completing circuit to control. Completed 

circuit to control will 

fi

 rst activate circulator 

and damper which will close end switch inside 

damper. Completes circuit to ignition system, 

ignition takes place.
In event boiler water temperature exceeds 

high limit setting on boiler mounted high limit 

control, power is interrupted between control 

system and ignition system. Power remains 

off until boiler water temperature drops below 

high limit setting. Circulator continues to 

operate under this condition until thermostat is 

satis

fi

 ed. 

In event 

fl

 ow of combustion products through 

boiler venting system becomes blocked, blocked 

vent safety switch shuts main burner gas off. 

Similarly, if boiler 

fl

 ue-way becomes blocked, 

fl

 ame rollout safety switch shuts main burner 

gas off.  Figure 16.

  

If either of these conditions 

occur, 

DO NOT ATTEMPT TO PLACE BOILER 

BACK INTO OPERATION. CONTACT 

CERTIFIED SERVICE AGENCY. 

Blocked Vent 

Safety Switch

Rollout Switch 

4 Section Boiler

Rollout Switch                        

2,3,5                    

Section Boiler

Intergral Draft 

Hood

Base

Burner 

Door

Burners

Ori

fi

 ces

Jacket Base 

Panel

Before seasonal start-up, have a certi

fi

 ed service agency 

check boiler for soot and scale in 

fl

 ues, clean burners and 

check gas input rate to maintain high operating ef

fi

 ciency.

WARNING

Label all wires prior to disconnection when servicing 

controls. Wiring errors could cause improper and 

dangerous operation.

!

  

Verify proper operation after servicing
Service agency will verify system is 

fi

 lled with water to 

minimum pressure and open air vents, if used, to expel any 

air accumulated in the system. Check entire piping system 

and, if any leaks appear, have them repaired.

Circulators need to be checked and maintained. 

Refer to circulator manufacturer's instructions.

Inspect venting system at the start of each heating 

season. Check vent pipe from boiler to chimney for signs of 

deterioration by rust or sagging joints. Repair if necessary. 

Remove vent pipe at base of chimney or 

fl

 ue and using a 

mirror, check vent for obstruction and verify vent is in good 

working order.
Boiler 

fl

 ue gas passageways may be inspected by a light 

and mirror. Remove burner door. Figure 17. Place trouble 

lamp in 

fl

 ue collector through draft relief opening. With 

mirror positioned above burners, 

fl

 ue gas passageways can 

be checked for soot or scale.

This procedure should be followed to clean 

fl

 ue gas 

passageways:

1. 

Remove burners from combustion chamber by raising 

burners up from manifold ori

fi

 ces and pulling toward 

front of boiler. Figure 19.

2. 

Disconnect vent pipe from draft hood.

3. 

Remove top jacket panel.

4. 

Remove combination 

fl

 ue collector and draft hood from 

boiler castings by loosening nuts on hold down bolts 

located on each side of collector. Figure 17.

5. 

Place sheet of heavy paper or similar material over 

bottom of base and brush down 

fl

 ue passageways. Soot 

and scale will collect on paper and is easily removed 

with the paper. 

6. 

With paper still in place in base, clean top of boiler 

castings of boiler putty or silicone used to seal between 

castings and 

fl

 ue collector. Verify chips are not lodged 

in 

fl

 ue passageways.

When cleaning process is complete, restore boiler 

components to their original position. Use IS-808 GE 

silicone (available from distributor) to seal around 

fl

 ue 

collector and boiler castings.

Figure 17 - Blocked Vent Safety Switch, Roll-out 

Safety Switch

Summary of Contents for MCB-100J

Page 1: ...ALLATION OPERATION MAINTENANCE MANUAL Models MCB 50J MCB 75J MCB 100J MCB 125J MCB 150J MCB 170J MCB 200J Tested For 100 psi ASME Working Pressure C S A Certified For Natural Gas Or Propane Manufactur...

Page 2: ...ns Pump size Supply Return Tappings A B C D E F 50 11 5 4 30 36 5 1 75 15 7 5 30 37 5 1 100 15 7 6 30 37 6 1 125 18 9 6 30 37 6 1 150 18 9 7 30 37 6 1 170 22 11 7 30 38 6 1 200 22 11 8 30 38 7 1 Propa...

Page 3: ...tory equipped supplied or specified components may result in personal injury or loss of life TO THE OWNER Installation and service of this boiler must be performed by a qualified installer TO THE INST...

Page 4: ...nput rate 4 for every 1000 ft 304m above sea level 2 Net AHRI Water Ratings shown based on piping and pickup allowance of 1 15 Consult manufacturer before selecting boiler for installations having unu...

Page 5: ...practical 7 Allow 24 inches 610mm at front and right side for servicing and cleaning 8 When installed in utility room door should be wide enough to allow largest boiler part to enter or to permit rep...

Page 6: ...H greater than 0 60 Volume 21 ft3 ACH x Total Input Mbh Refer to National Fuel Gas Code for opening requirements between connection indoor spaces All Outdoor Air Provide permanent opening s communicat...

Page 7: ...of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in di...

Page 8: ...on 5 Hot water boilers and system must be filled with water and maintained to minimum pressure of 12 psi 6 Bypass piping is optional which gives ability to adjust supply boiler water temperature to fi...

Page 9: ...NING Burn and scald hazard Safety relief valve could discharge steam or hot water during operation Install discharge piping per these instructions 8 Install discharge piping from safety relief valve S...

Page 10: ...10 4 CONNECTING SUPPLY AND RETURN PIPING Figure 6 Single Zone System With DHW Figure 7 Multi Zone System With Circulators And DHW...

Page 11: ...11 4 CONNECTING SUPPLY AND RETURN PIPING Figure 8 Multi Zone System With Zone Valves And DHW With Circulator Figure 9 Multi Zone System With Zone Valves And DHW With Zone Valve...

Page 12: ...nting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an...

Page 13: ...ocation following installation 5 Thermostat s heat anticipator must be adjusted to match total current draw of all controls associated with boiler during heating cycle 7 VENT DAMPER INSTALLATION INSTR...

Page 14: ...ping Pressure test boiler and gas connection before placing boiler in operation Pressure test over 1 2 psig 3 5 kPa Disconnect boiler and its individual gas shutoff valve from gas supply system Pressu...

Page 15: ...at on outside wall 3 Do not install thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions fireplace or chimney 4 Check thermostat operation by raising...

Page 16: ...M Figure 13 Integrated High Limit Electronic Ignition Control 240008781 WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal inj...

Page 17: ...Appliance and call qualified service technician or your gas supplier TO TURN OFF GAS TO THE APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if service i...

Page 18: ...if used to expel any air accumulated in the system Check entire piping system and if any leaks appear have them repaired Circulators need to be checked and maintained Refer to circulator manufacturer...

Page 19: ...pilot flame Be sure to replace cover screw after adjustment to prevent possible gas leakage See Figure 16 Page 19 Check burners and pilot for signs of corrosion rust or scale buildup Area around boil...

Page 20: ...water column from specified pressure listed on boiler rating plate Primary air adjustment is not necessary therefore air shutters are not furnished as standard equipment CHECK SAFETY CONTROL CIRCUIT T...

Page 21: ...lified service agency prior to resuming operation 4 ECONOMY Active Indicates thermal targeting function is active and limit control is reducing boiler temperature to conserve fuel Economy feature is a...

Page 22: ...NOTES...

Page 23: ...Date Service Performed Company Name Tech Initials Company Address Phone...

Page 24: ...COLUMBIA BOILER COMPANY Main offices and factory Pittstown PA...

Reviews: