background image

 

Installation Procedure 

 

 

 
1)

 

Inspect the boiler package to ensure that no damage occurred during shipment.  
Please contact the distributor immediately if there is any sign of damage. 

 
2)

 

Maintain the boiler package in its protective crate as long as possible to prevent any 
damage when positioning the boiler.  When the boiler package is located adjacent to 
its final position, the protective crate may be removed by first cutting the banding 
(Note: bands are under tension and will spring back when cut) and then by prying the 
individual crate panels.  In addition, remove the lag bolts which hold the boiler onto 
the skid.  

 
3)

 

Place the boiler on a level floor as near to the chimney as possible.  Adhere to the 
following minimum clearances to combustible material: 

 

a.

 

Floor – Non Combustible Floor Only 

b.

 

Sides – 6” 

c.

 

Rear – 6” 

d.

 

Front – 24” 

e.

 

Top – 38” 

f.

 

Chimney Connector (Vent Pipe) – 18” 

 

For clearances less than the listed values, please consult National Fire Protection 
Agency (NFPA) -54 National Fuel Gas Code Table 6.2.3(B). 
 

4)

 

Ensure that there is adequate combustion air for the burner.  Lack of adequate 
combustion air may result in noisy combustion, erratic burner operation, and/or 
nuisance lock outs.  In addition, the lack of combustion air will result in a shift of the 
burner’s performance curve and may result in the generation of CO gases inside of 
the heat exchanger.  Please refer to the Start Up Procedure & Annual Maintenance 
Requirement sections for instructions on setting up and servicing the burner.  

 

For installations in utility rooms or closets, it is necessary to provide two separate 
ventilation openings in the door (one located at 12” and the other 60”).  Each opening 
shall be 160 square inches in size.  For installations in buildings with tight 
construction (little fresh air infiltration), it is necessary to place an opening in the 
exterior wall that is 160 square inches in size and is located adjacent to the boiler. 

 
5)

 

Install piping for the hydronic and domestic hot water systems.  Utilize the 1-1/4” 
coupling located on top of the boiler for the hydronic system supply and the 1-1/4” 
nipple at the midpoint of the front face for the hydronic system return.  Connect the 
hot water system to the 1/2” copper fittings located on the coil plate.  The right side 
adapter is for incoming cold water and the left side for outgoing hot water.  Pipe the 
hydronic and hot water systems as detailed in the following figure.  Ensure that all 
fittings are tight before filling the system. 

Unit installation must be performed only by a qualified serviceman 
that is familiar with state and local codes. 

 

 

 

 

 

 

W

W

W

a

a

a

r

r

r

n

n

n

i

i

i

n

n

n

g

g

g

:

:

:

 

 

 

Summary of Contents for EMG-31 120

Page 1: ... ri ie es s B Bo oi il le er rs s Available in Natural Gas Propane Rev 12012 Columbia Boiler Company PO Box 1070 Pottstown PA 19464 Tel 610 473 8457 Fax 610 367 6800 Website www columbiaboiler com Email cbcsales ptd net ...

Page 2: ...to replace any part of the control system and any gas control which has been under water Operating Instructions Quick Reference 1 Read all instructions prior to operating equipment 2 Set the thermostat to the lowest setting 3 Turnoff all electric power to the appliance 4 This device is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 5 I...

Page 3: ...instruction manual carefully The information contained within is designed to help you maintain peak performance from your unit Product Features ASME Coded Boiler Registered with National Board Factory Mounted Wired Burner and Controls Fully Insulated Heat Exchanger with Powder Coated Cabinet Packaged with Standard Five Gallon per Minute Tankless Coil Domestic Hot Water Equipped with Triple Aquasta...

Page 4: ...e Size 0 242 11 64 0 250 13 64 0 290 7 32 Fuel Input Rate Cfm 1 95 0 79 2 28 0 95 2 60 1 06 Max Inlet Pressure W C 11 11 11 11 11 11 Min Inlet Pressure W C 5 5 5 5 5 5 Manifold Pressure W C 3 5 3 5 3 5 3 5 3 5 3 5 Head Position Factory Set Factory Set Factory Set Factory Set Factory Set Factory Set Air Shutter 31 30 45 42 65 78 Draft Over Fire W C 0 02 0 02 0 010 0 02 0 005 0 005 Draft in Stack W ...

Page 5: ...dth 21 C Hydronic Supply Height 43 D Coil Supply Height 41 E Burner Height 8 1 2 F Hydronic Return Height 21 1 2 G Flue Pipe Diameter 6 H Washout 21 1 2 I Jacket Depth Including Flange 21 Depth Front to Rear w Burner 29 3 4 Hydronic Supply Size 1 1 4 Hydronic Return Size 1 1 4 Washout Size 3 4 ...

Page 6: ...ombustion air will result in a shift of the burner s performance curve and may result in the generation of CO gases inside of the heat exchanger Please refer to the Start Up Procedure Annual Maintenance Requirement sections for instructions on setting up and servicing the burner For installations in utility rooms or closets it is necessary to provide two separate ventilation openings in the door o...

Page 7: ...7 Note Installer responsible for ensuring that piping conforms to all applicable codes ...

Page 8: ... boiler has been filled with water until entire system has been purged of air System pressure must not exceed 30 PSI 11 Check burner and install desired orifice See burner manual for instructions All units are shipped from the factory with an orifice for each firing rate and natural gas or LP gas Select the correct orifice for you application from the chart in this manual and install per burner in...

Page 9: ...installing a listed draft inducer or draft regulator 23 Take a CO2 measurement using a combustion analyzer Adjust the air shutter so that the CO2 reading measures 9 0 Increase the air shutter opening to decrease the CO2 value and decrease the air shutter opening to increase the value 24 Use the combustion analyzer to verify that the CO level is below 100 ppm and that the flue temperature is above ...

Page 10: ...highest point of piping Trouble Too Much Heat Source Procedure Causes Remedy Circulator Check to see if Aquastat is operating properly Circulator does not stop running Repair Thermostat Check thermostat settings and calibration Thermostat set too high Reset thermostat Thermostat defective Replace thermostat Thermostat out of calibration Recalibrate thermostat Flow Valve Check to see if flow valve ...

Page 11: ...king in partially closed position Flow valve not opening fully Clean or replace flow valve Radiation Check radiators for air Radiators air bound Bleed radiators Check to ensure radiators are properly sized Radiators inadequate Install alternate radiators Boiler Determine required heat load Boiler too small for application Additional heating capacity required Tankless Coil Check usage of domestic h...

Page 12: ...for Flue Box 25 spool 790330 Columbia Blank Coil Plate with 1 8 and 3 4 Tapping 481011 Columbia Coil Gasket 530675 Columbia 5 Gallon Coil Assembly with Gasket Boxed 337350 FT Fire Chamber 221750 FT Base Assembly Boiler Accessory Part Numbers 535030 Taco 007 Circulator Pump 559560 Altitude Gauge 1 4 x 2 1 2 Round 575020 Relief Valve 3 4 Male ...

Reviews: