3
NOTES:
• Greater clearances for access should supersede fire pro
-
tection clearances.
* For installation on combustible flooring Special Base MUST
BE USED. (See Replacement Parts Section)
1. Keep boiler area clear and free from combustible
materials, gasoline and other flammable vapors
and liquids.
2.
DO NOT
obstruct air openings to the boiler
room.
3. Modification, substitution or elimination of factory
equipped, supplied or specified components may
result in property damage, personal injury or the
loss of life.
4.
To The owner:
Installation and service of
this boiler must be performed by a qualified
installer.
5.
To The insTaller:
Leave all instructions with
the boiler for future reference.
6. When this product is installed in the Com
-
monwealth of Massachusetts the installation
must be performed by a Licensed Plumber
or Licensed Gas Fitter.
Improper installation, adjustment, alteration,
service or maintenance can cause injury or
property damage.
INTRODUCTION
The installation must conform to the requirements of
1.
the authority having jurisdiction or, in absence of such
requirements, to the latest revision of the National Fuel
Gas Code, ANSI Z223-1. (Available from the American
Gas Association, Pleasant Valley Road, Cleveland, Ohio
44134.) Reference should also be made to local gas utility
regulations and other codes in effect in the area in which
the installation is to be made.
Where required by the authority having jurisdiction, the
2.
installation must conform to American Society of Me
-
chanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME No.
CSD-1.
This boiler is classified as a Category I and III and vent
3.
installation shall be in accordance with the latest revision
of the National Fuel Gas Code, ANSI Z223.1 or applicable
provisions of the local building codes.
LOCATE BOILER on level, solid base as near the outside
4.
wall as possible and centrally located with respect to the
heat distribution system as practicable.
Allow 24 inches at the front and right side for servicing
5.
and cleaning.
When installed in utility room, the door should be wide
6.
enough to allow the largest boiler part to enter, or to
permit replacement of another appliance such as a water
heater.
The boiler shall be installed such that the gas ignition
7.
system components are protected from water, (dripping,
spraying, rain, etc.), during appliance operation and
service, (circulator replacement, condensate trap, control
replacement, etc.).
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS
8.
ONLY. *The boiler must not be installed on carpeting.
Minimum clearances to combustible constructions are:
TOP ...................................................... 18 IN.
FRONT .....................................................6 IN.
FLUE CONNECTOR
...............................6 IN.
REAR ........................................................4 IN.
CONTROL SIDE .......................................9 IN.
OTHER SIDE ...........................................3 IN.
VENT PIPE ..............................................6 IN.
WARNING
!
WARNING
!