MECHANICAL SPECIFICATIONS

MANUFACTURE AND CERTIFICATIONS

• Units shall be manufactured in an ISO 9001 certified facility.

• Units shall be certified by CSA to UL 1995 / CSA 22.2 and

performance certified to ANSI/AHRI Standard 210/240.

• Units shall be sound tested according to ANSI/AHRI Stan-

dard 270.

• Certified matched system ratings will be available for down-

load from the AHRI online directory at www.ahridirectory.org

• Unit packaging shall be marked, “Assembled in the USA”

UNIT APPLICATION

• Units shall be approved for cooling operation between 50ºF

and 120ºF without modification.

• Units shall be approved for linesets up to 200 feet equivalent

length without modification.

• Units shall be approved for installation within 6 inches of a

flat vertical wall without modification, according to the
instructions in the technical literature.

• Units shall be certified for seismic applications in accordance

with CBC 2007 and IBC 2006.

• Units shall be designed to 72dBA or less to minimize sound

pollution.

UNIT ACCESS

• Units shall have a fan guard that can be removed inde-

pendently of the cabinet for access to the condenser coil.

• Units shall have blow-through airflow for the condensing coil.

• Units shall have a separate compartment for electrical con-

trols that can be accessed without disturbing the unit airflow.

UNIT CONSTRUCTION

• Units shall be shipped completely wired, piped and assem-

bled. Wiring pigtails shall be provided for field control wiring
connections. Service valves shall be provided for field refrig-
erant line connections.

• Units shall be factory leak checked, run tested, and shipped

with a holding charge of R-410A refrigerant.

• Unit cabinet components shall be G90 equivalent steel fin-

ished with powder-coat paint rated at a minimum of 1,000
hours under ASTM B117 testing.

• Unit base pan shall be stamped G90 equivalent steel fin-

ished with powder-coat paint rated at a minimum of 1,000
hours under ASTM B117 testing.

• Units shall have a factory installed filter drier for faster instal-

lation and improved system reliability.

• Units shall be constructed with a high pressure switch and a

low pressure switch for system protection.

UNIT COMPONENTS

• Compressor shall be hermetic with internal electrical over-

load protection and internal overpressure protection.

• Compressor shall be mounted on rubber vibration isolators

that do not require the removal of transportation clips or
brackets.

• Units shall be constructed with scroll compressors.

• Outdoor fan shall be direct drive with horizontal air dis-

charge.

• Outdoor fan shall be direct drive with swept-wing blades for

low sound levels.

• Outdoor coil shall be air cooled and constructed of zinc-

coated aluminum microchannel construction for small size
and low weight.

UNIT WARRANTIES

• Unit manufacturer shall provide a 10-Year compressor war-

ranty without a requirement for unit registration.

• Unit manufacturer shall provide a 5-Year parts warranty with-

out a requirement for unit registration.

Summary of Contents for TCHE36S43S1

Page 1: ...footprint is lim ited these units can be stacked two high using the approved stacking kit FEATURES Performance Optimized for the US DOE Southwest Region and valid for installation in all US DOE Regio...

Page 2: ...TALLATION 10 MOUNTING HOLE GRAPHIC 10 TYPICAL FIELD WIRING 10 PERFORMANCE DATA 3 TON 11 PERFORMANCE DATA 4 TON 13 NOMENCLATURE BRAND T T Factory Branded PRODUCT TYPE C C Air Conditioner US Northern or...

Page 3: ...ual for Hard Start Kit part number for each model No No No No Fan Diameter Inches 23 23 23 23 Fan Motor Rated HP 1 4 1 4 1 4 1 4 Rated Load Amps 1 3 1 3 0 8 0 8 Nominal RPM 850 850 850 850 Nominal CFM...

Page 4: ...tain system performance 3 Systems matched with furnaces or air handlers not equipped with blower off delays may require 60 second time delay 4 CF and FC coils cannot be used in horizontal applications...

Page 5: ...4 3 4 S1 TM8Y080C16MP11 21 0 FC38C 1200 35 8 27 2 15 50 12 75 TCHE36S4 3 4 S1 TM8Y100C16MP11 21 0 FC38C 1200 35 8 27 2 15 50 12 75 TCHE36S4 3 4 S1 TM8Y100C20MP11 21 0 FC38C 1200 35 6 27 0 15 25 12 75...

Page 6: ...1 TL9E080C16UH11 21 0 FC49D 1225 45 5 32 4 14 75 12 25 TCHE48S4 3 4 S1 TL9E100C20UH11 21 0 FC49D 1400 46 5 34 6 15 00 12 25 TCHE48S4 3 4 S1 TM8E080C16MP11 21 0 FC49D 1250 45 5 32 6 15 00 12 25 TCHE48S...

Page 7: ...75 12 25 TCHE48S4 3 4 S1 TMLV100C20MP11C 21 0 FC49D 1425 46 0 34 2 15 00 12 50 TCHE48S4 3 4 S1 TMLV100C20MP12C 21 0 FC49D 1225 45 5 32 4 15 00 12 50 TCHE48S4 3 4 S1 TMLV120C20MP11C 21 0 FC49D 1425 46...

Page 8: ...ver a wide range of conditions See System Charge Table Price Pages or Source1 Smart Search for TXV part number for each AC HP model Cold Weather Charging Tent S1 CHGTENT01 Provides warm environment to...

Page 9: ...completely wired piped and assem bled Wiring pigtails shall be provided for field control wiring connections Service valves shall be provided for field refrig erant line connections Units shall be fa...

Page 10: ...NOTES ALL OUTDOOR WIRING MUST BE WEATHERPROOF CAN BE STACKED TWO HIGH WITH APPROVED STACKING KIT AIRFLOW DIRECTION 28 06 7 50 18 73 LARGE CABINET ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC COD...

Page 11: ...34 3 34 3 29 0 28 3 22 0 35 7 37 0 31 1 30 1 22 8 K W 1 89 1 91 1 88 1 90 1 92 1 96 1 98 1 96 1 98 2 00 2 04 2 06 2 05 2 06 2 09 65 55 T C 33 2 35 7 35 7 38 7 41 4 34 7 36 8 36 7 39 7 42 2 36 2 37 9 3...

Page 12: ...01 1 01 0 98 TMLE100B12MP11 FC38C 1 01 0 97 1 00 TMLE100C16MP11 FC38C 1 01 0 97 0 98 TMLE100C20MP11 FC38C 1 01 1 01 0 98 TMLE120C16MP11 FC38C 1 01 0 97 0 98 TMLE120C20MP11 FC38C 1 01 1 02 0 98 TMLV080...

Page 13: ...9 27 0 K W 2 46 2 48 2 48 2 50 2 55 2 54 2 56 2 56 2 58 2 64 2 62 2 64 2 64 2 67 2 73 65 55 T C 43 7 46 1 46 3 48 5 51 2 45 1 47 1 47 3 49 4 52 0 46 6 48 2 48 3 50 2 52 9 S C 42 3 39 0 33 5 31 7 26 1...

Page 14: ...20MP11C FC49D 1 00 0 99 0 99 TM9V100C20MP12C FC49D 0 99 0 96 0 98 TM9V120D20MP11C FC49D 1 00 1 00 0 97 TM9V120D20MP12C FC49D 0 99 0 95 0 96 TM9Y100C16MP11 FC49D 1 00 1 02 1 03 TM9Y100C20MP11 FC49D 1 0...