Coleman TCHE36S43S1 Technical Manual Download Page 2

5371957-CTG-D-0120

2

Johnson Controls Ducted Systems

LIST OF SECTIONS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PHYSICAL AND ELECTRICAL DATA  . . . . . . . . . . . . . . . . . . . . . . . 3
DIMENSIONS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS . . . . . . . 4
COOLING CAPACITY - With Air Handler Coils  . . . . . . . . . . . . . . . 4
COOLING CAPACITY - Upflow, Downflow & 
Horizontal Furnaces and Coils (Coil Only Ratings)   . . . . . . . . . . . 4
COOLING CAPACITY - With High Efficiency Motor Furnaces  . . . 5
APPLICATIONS AND ACCESSORIES   . . . . . . . . . . . . . . . . . . . . . . 8
SOUND POWER RATINGS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MECHANICAL SPECIFICATIONS  . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TYPICAL INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MOUNTING HOLE GRAPHIC  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TYPICAL FIELD WIRING   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PERFORMANCE DATA - 3 TON   . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PERFORMANCE DATA - 4 TON   . . . . . . . . . . . . . . . . . . . . . . . . . . 13

NOMENCLATURE

BRAND

T

T

 = Factory Branded

PRODUCT TYPE

C

C

 = Air Conditioner 

(US Northern or Southeast Region)

AIRFLOW

H

H

 = Horizontal Discharge

NOMINAL
SERIES EFFICIENCY
AND STAGING

E

E

 = 14 SEER High EER 

(US DOE Southwest Region)

NOMINAL
UNIT CAPACITY
(MBH)

36

36

 = 3 Ton

48

 = 4 Ton

STAGING

S

= Single Stage Compressor

REFRIGERANT

4

= R-410A Refrigerant

VOLTAGE
(Voltage-Phase-Hertz)

3

3

 = 208/230-3-60

4

 = 460-3-60

CONNECTION TYPE

S

= Sweat Connect

GENERATION
(MAJOR REVISION)

1

1

 = 1st Gen

2

 = 2nd Gen

etc

STYLE LETTER
(MINOR REVISION)
NOT USED 
FOR ORDERING

A

A

 = Style A

B

 = Style B

etc

Summary of Contents for TCHE36S43S1

Page 1: ...footprint is lim ited these units can be stacked two high using the approved stacking kit FEATURES Performance Optimized for the US DOE Southwest Region and valid for installation in all US DOE Regio...

Page 2: ...TALLATION 10 MOUNTING HOLE GRAPHIC 10 TYPICAL FIELD WIRING 10 PERFORMANCE DATA 3 TON 11 PERFORMANCE DATA 4 TON 13 NOMENCLATURE BRAND T T Factory Branded PRODUCT TYPE C C Air Conditioner US Northern or...

Page 3: ...ual for Hard Start Kit part number for each model No No No No Fan Diameter Inches 23 23 23 23 Fan Motor Rated HP 1 4 1 4 1 4 1 4 Rated Load Amps 1 3 1 3 0 8 0 8 Nominal RPM 850 850 850 850 Nominal CFM...

Page 4: ...tain system performance 3 Systems matched with furnaces or air handlers not equipped with blower off delays may require 60 second time delay 4 CF and FC coils cannot be used in horizontal applications...

Page 5: ...4 3 4 S1 TM8Y080C16MP11 21 0 FC38C 1200 35 8 27 2 15 50 12 75 TCHE36S4 3 4 S1 TM8Y100C16MP11 21 0 FC38C 1200 35 8 27 2 15 50 12 75 TCHE36S4 3 4 S1 TM8Y100C20MP11 21 0 FC38C 1200 35 6 27 0 15 25 12 75...

Page 6: ...1 TL9E080C16UH11 21 0 FC49D 1225 45 5 32 4 14 75 12 25 TCHE48S4 3 4 S1 TL9E100C20UH11 21 0 FC49D 1400 46 5 34 6 15 00 12 25 TCHE48S4 3 4 S1 TM8E080C16MP11 21 0 FC49D 1250 45 5 32 6 15 00 12 25 TCHE48S...

Page 7: ...75 12 25 TCHE48S4 3 4 S1 TMLV100C20MP11C 21 0 FC49D 1425 46 0 34 2 15 00 12 50 TCHE48S4 3 4 S1 TMLV100C20MP12C 21 0 FC49D 1225 45 5 32 4 15 00 12 50 TCHE48S4 3 4 S1 TMLV120C20MP11C 21 0 FC49D 1425 46...

Page 8: ...ver a wide range of conditions See System Charge Table Price Pages or Source1 Smart Search for TXV part number for each AC HP model Cold Weather Charging Tent S1 CHGTENT01 Provides warm environment to...

Page 9: ...completely wired piped and assem bled Wiring pigtails shall be provided for field control wiring connections Service valves shall be provided for field refrig erant line connections Units shall be fa...

Page 10: ...NOTES ALL OUTDOOR WIRING MUST BE WEATHERPROOF CAN BE STACKED TWO HIGH WITH APPROVED STACKING KIT AIRFLOW DIRECTION 28 06 7 50 18 73 LARGE CABINET ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC COD...

Page 11: ...34 3 34 3 29 0 28 3 22 0 35 7 37 0 31 1 30 1 22 8 K W 1 89 1 91 1 88 1 90 1 92 1 96 1 98 1 96 1 98 2 00 2 04 2 06 2 05 2 06 2 09 65 55 T C 33 2 35 7 35 7 38 7 41 4 34 7 36 8 36 7 39 7 42 2 36 2 37 9 3...

Page 12: ...01 1 01 0 98 TMLE100B12MP11 FC38C 1 01 0 97 1 00 TMLE100C16MP11 FC38C 1 01 0 97 0 98 TMLE100C20MP11 FC38C 1 01 1 01 0 98 TMLE120C16MP11 FC38C 1 01 0 97 0 98 TMLE120C20MP11 FC38C 1 01 1 02 0 98 TMLV080...

Page 13: ...9 27 0 K W 2 46 2 48 2 48 2 50 2 55 2 54 2 56 2 56 2 58 2 64 2 62 2 64 2 64 2 67 2 73 65 55 T C 43 7 46 1 46 3 48 5 51 2 45 1 47 1 47 3 49 4 52 0 46 6 48 2 48 3 50 2 52 9 S C 42 3 39 0 33 5 31 7 26 1...

Page 14: ...20MP11C FC49D 1 00 0 99 0 99 TM9V100C20MP12C FC49D 0 99 0 96 0 98 TM9V120D20MP11C FC49D 1 00 1 00 0 97 TM9V120D20MP12C FC49D 0 99 0 95 0 96 TM9Y100C16MP11 FC49D 1 00 1 02 1 03 TM9Y100C20MP11 FC49D 1 0...

Reviews: