background image

 

13

 
Inspectors generally insist that a breaker or disconnect be located as close to the energy source as possible and may 
also insist on a 2

nd

 breaker or disconnect near its final termination point.  Please consult NEC regulations and your 

local inspector to determine the requirements in your area.  These subjects are outside of the scope of this manual; 
however, it is your responsibility to ensure your unit is installed safely! 
 
Solar panels and Wind/Hydro turbines are energy sources.  A breaker or fuse is required between these devices and 
any other components (including the HVAD).  Do not hook up a wire from any energy source into the HVAD 
without the ability to quickly and safely disconnect the input.  All inputs need fuses or breakers! 
 
Wiring the controller. 
 
Please refer to the large hookup diagram at the beginning of this manual.   
 
The positive wire from the battery (which is routed through a breaker) is connected to the left most bottom terminal.  
Please remove the nut and washer and place your wire terminal under the washer but above the large red wire that is 
already present.  
 
The solar panels connect to the 2

nd

 terminal from the left (through a breaker of course.). 

 
The wind/hydro energy source connects to the 3

rd

 terminal from the left (via a breaker). 

 
The three terminals on the far right are shared negatives.  Connect at least one large wire from one of these terminals 
to the negative post (or buss) of your battery bank.   Solar and hydro negative leads can be wired here as well; 
however, it is generally better to wire them directly to the negative post (or buss) of the battery bank. 
 
As mentioned above, when the solenoid is not enabled, the solar input is electrically connected via the normally 
closed (connected) contacts of the solenoid, to the positive post (buss) of your battery bank. This means that the solar 
positive is hooked directly to your battery positive during the idle state of the solenoid.  When the solenoid is engaged 
(the coil is active), the solenoid’s bottom contacts open and disconnect the electrical connection from the solar panels 
to your battery bank.  
 
The wind/hydro input is not switched (disconnected and connected) by the solenoid.  This input is always connected 
directly to your battery bank.  The only electrical reason this input is provided at the controller is for monitoring 
purposes. As the current passes though the controller (and the turbine shunt located on the upper right of the 
controller), the microprocessor is able to determine the current flow of your turbine.  This input also passes though the 
breaker on the right side of the unit. This breaker allows the turbine input to be disconnected for diagnostic purposes, 
but again, this does not fulfill the requirement of having an over-current protection device between the turbine and the 
controller. 
 
The diversion load (real or dummy) if used, must be hooked to the middle two terminals on the left side of the unit.  
Most resistive devices (heaters) are not polarity sensitive; so in this case, it does not matter which terminal is wired to 
which input of the load.  Other loads, such as inverters, pumps, power supplies etc, are polarity sensitive and must be 
hooked up with the correctly polarity.  The upper terminal (of these two terminals) is the positive connection.  This is 
the terminal that has the aluminum strap connected to it that crosses over the top of the solenoid.  The lower terminal 
is the negative terminal for your load and is electrically connected to the three terminals on the lower left of the 
controllers.  The normally open contacts of the solenoid (the two that stick out the sides of the solenoid), are used to 
control the diversion load.  The diversion load is enabled (connected to the battery) when the solenoid is enabled.

 

 

 
No diversion load is required for a solar only installation. 
When the batteries reach the trip point, the solar energy 
will be disconnected from the batteries until the batteries drop.  Diversion loads can however be used with solar only 
installations and/or solar/hydro combined installations when the excess energy is desired to run “real” loads.  In this 

Summary of Contents for C440-HVAD

Page 1: ...e managed through the user interface Relay on time can be controlled and set for diversion times up to several hours Upper and lower set points can both be set Automatic LCD back light dimming to save...

Page 2: ...ies to complete a full charge of the batteries The internal LED on the upper left of the large PCB board motherboard is lighted when the solenoid is engaged The red LED on the small daughter board is...

Page 3: ...3...

Page 4: ...select the current value and then press the up button to exit the menu For example To change the float set point of the controller Press the Enter Up Down or Scroll button on the front panel The Charg...

Page 5: ...mechanical controller that does have the ability to track multiple voltages and react accordingly Additional charging logic has also been added including such features as re bulking an absorb mode th...

Page 6: ...solid state controller and may allow the voltage to rise or fall further than optimal To alleviate this condition it is recommended that your charge source s not exceed the battery bank s amp hour ca...

Page 7: ...state of the solenoid of less than two seconds Given these settings the controller may turn on and off the solenoid several times per minute This is great if you want to keep the batteries as close to...

Page 8: ...n it is connected to the batteries The solar VOC reading will only be accurate when the solenoid is enabled Hint Run the test cycle to watch how the enable disable of the solenoid affects the solar vo...

Page 9: ...you may hear the solenoid s coil pull in as normal but see no difference in the solar amperage or solar voltage during the test This generally indicates the normally closed contacts of the solenoid ar...

Page 10: ...the batteries along with the load the turbine remains more within its design realm always a good thing Please note this controller does not include a blocking diode or an A C to D C rectifier as thes...

Page 11: ...designed specifically for 12 24 and 48 volt systems are by far a better choice A very acceptable diversion load is a power resistor These can be obtained via your Coleman Air dealer Various wattages a...

Page 12: ...use the front panel buttons and display When mounting vertically the inputs of the controller should always be oriented downwards with the vent upwards to ensure the unit is able dissipate any captiv...

Page 13: ...d the coil is active the solenoid s bottom contacts open and disconnect the electrical connection from the solar panels to your battery bank The wind hydro input is not switched disconnected and conne...

Page 14: ...ircuits but they may be no competition to a direct lighting hit Many of our controllers have survived direct lighting hits due to the internal protective circuits yet the connected equipment like mete...

Page 15: ...eries will be allowed to drop percentage based Once the batteries reach the upper trip point you have set the same trip point as the non EDM mode the controller will engage and disengage the solenoid...

Page 16: ...tandby current 1W 15W 3W Energy consumed by the electronics meters on solenoid on 1A 75A 5A Minimum float setting volts 12 0 24 48 Maximum float setting volts 24 48 96 Factory default float setting vo...

Page 17: ...witch can offer such a level of reliability For such systems our solid state controllers no relays or solenoids should be considered To replace the solenoid 1st ensure all power is removed from the un...

Page 18: ...ms should be designed for no more than 125 amps continuous current Higher voltage higher amperage systems will result in a lower life expectancy of the solenoid We recommend our solid state controller...

Reviews: