background image

7.11.   Configuring Parameters.

7.11.1. To select the parameter, enter Programming mode by pressing               and              

button for 5 seconds.

 

Use the               and               buttons to select the parameter for modification.

 

Press the                button to display the value.

 

By keeping the              button pressed, use the               and               buttons to set 
the desired value.

 

When the button              is release, the newly programmed value will be stored.

 

The newly programmed value is stored and the following parameter is displayed.

 

To exit from the setup, press the              or wait for 30 seconds.

15

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Page 15 of 24 

 M6493 Issue 10.3 

7.11. 

Configuring Parameters. 

7.11.1. 

To select the parameter, enter Programming mode press 

 

and

 

 

button for 5 seconds. 

Use the 

 and 

 buttons to select the parameter for modification. 

Press the 

 button to display the value. 

By keeping the 

 button pressed, use the 

 and 

 buttons to 

set the desired value. 

When the 

 button is release, the newly programmed value will be stored. 

The newly programmed value is stored and the following parameter is displayed. 

To exit from the setup, press the 

 or wait for 30 seconds. 

PAR 

RANGE 

DESCRIPTION 

SCL 

1°C; 
2°C; 
°F 

Read out scale (see Input Specification table on page 17) 

Caution: upon changing the SCL value, it is the absolutely necessary to reconfigure the 

parameters relevant to the absolute and relative temperatures (SPL, SPH, 1SP, 1HY etc.). 

SPL 

-50°..SPH

Minimum limit for 1SP setting. 

SPH 

SPL..150°C 

Maximum limit for 1SP setting. 

1SP 

SPL..SPH 

Set-point (value to be maintained in the room). 

1CM 

HY;PID 

Control mode. 
With 1CM=HY you select control with hysteresis: parameters 1HY, 1T0 and 1T1 are used. 
With 1CM=PD you  select a Proportional-Integral-Derivative control mode: parameters 1PB, 1IT, 
1DT, 1AR, 1CT will be used. 

1CH 

REF;HEAS 

Refrigerating (REF) or Heating (HEA) control mode. 

 1

CM

=

H

Y

 

1HY 

0…19.9°C 

OFF/ON thermostat differential. With 1HY =

 

0 the output is always off. 

1TO 

0…30min 

Minimum off time. 
After output 1 has been turned off’ it remains inactive for 1TO minutes regardless of the 
temperature value measured. 

1T1 

0…30 min 

Minimum on time. (The following parameter will be 1PF). 
After output 1 has been turned on, it remains active for 1T1 minutes regardless of the 
temperature value measured. 

1

C

M

=

P

ID 

1PB 

0.19.0°C 

Proportional bandwidth. 

Temperature control takes place by changing the 

ON time to the output: the closer the temperature 

to the set-point, the less time to activate. A small 

proportional band increases the promptness of the 

response of the system to temperature variations, 

but tends to make it less stable. A purely 

proportional control stabilises the temperature 

within the proportional band but does not cancel 

the deviation from the set-point. 

With 

1PB=0

 the output is always off. 

On/Off heating control

(

1CM

 = HY, 

1CH

 + HEA).

On/Off refrigeration control

(

1CM

 = HY, 

1CH

 + REF).

Page 12 of 24                                                                                                                                  M6493 Issue 10.3 

7.3.3.  Proportional, Integral and Derivative Control. 
 

A proportional controller continuously adjusts the power, so the heat input to 
the process is approximately in balance with the process heat requirements 
in order to maintain a stable temperature. The range of temperature over 
which power is adjusted is from 0% to 100%. This temperature range is 
called the ‘Proportional Band’. The proportional band is adjustable for 
differing process conditions (zero proportional band returns the controller to 
basic on / off control). 
 
The temperature difference between the stabilised temperature and the set 
point is called the ‘Offset’. The offset can be reduced by adjusting the integral 
term of the PID controller. This is achieved using the integrative action time 
and integrative action reset. 
 
A derivative function can be combined with the proportional controller to 
provide the controller with the ability to shift the proportional band either up to 
or down to compensate for rapidly changing temperature (i.e. when an oven 
door is opened or cooler fluid is introduced into a controlled vessel). The 
derivative function increases the controller gain during temperature changes, 
and can help to reduce overshoot on start-up. 
 
Hence, a three-mode PID controller combines the proportional, integral and 
derivative actions, to allow the set point temperature to be approached 
relatively smoothly with minimal overshoot. 

 

7.4.  Front Panel Controls 
 

The MC810B controller has four front panel keys as described below. 
 

7.4.1.  The 

 

 

key is used to increase the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.2.  The 

 

key is used to decrease the value of the parameter shown on 

the display or to scroll through the parameter menu. 

 

7.4.3.  The 

 

key is a dual function key. It  is used to display and store the 

value of the selected parameter when in ‘Programming’ mode. When used with 

the 

 it is used to display the ‘Setpoint’ value. 

 

7.4.4.  The 

 

is an ‘Exit / Stand-by button. Press of 3 seconds to turn unit on 

or off. 

 

7.5.  Operating Modes. 
 

7.5.1.  The MB810B has two modes of operation: Function mode and Programming 

mode. The unit enters Function mode immediately following power up in auto 
test phase. In Function mode the display shows the temperature measured by 
the temperature sensing probe. The output power will also be switched on or off 
as appropriate. If the output power is on, the amber neon indicator on the front 
panel will be illuminated. The only parameter which can be altered in the 
function mode is the set-point. See 7.7.1 

 

7.5.2.  In Programming mode, all the other parameters apart from set-point can be 

altered. To gain access to the programming mode from Function mode, press 

the keys 

 

and

 

 

. Keep them pressed for five seconds. The 

output power is always off when in programming mode. If approximately 25 
seconds elapse while in programming mode with out a key being pressed the 

Summary of Contents for CN-200D Series

Page 1: ...Cole Parmer CN 200D Series Digital Controllers Instruction Manual M6493 Version 10 6...

Page 2: ...ation of Conformity 23 The copyright of this instruction manual is the property of Antylia Scientific Limited This instruction manual is supplied by Antylia Scientific Limited on the express understan...

Page 3: ...resistance probe The sample temperature is displayed on the LED display This product is suitable for bench and retort stand mounting or wall mounting using the bracket and screws provided 1 3 The CN...

Page 4: ...ify Setpoint 2 button Exit Standby button Alarm This feature is not available on CN 200D 4 Page 4 of 24 M6493 Issue 10 3 2 SYMBOLS AND USING THIS INSTRUCTION BOOK 2 1 Throughout this Instruction book...

Page 5: ...uct so that it is difficult to disconnect from the mains supply Do not immerse unit in water or fluids Do not spill substances onto this unit If spillage does occur disconnect unit from mains supply a...

Page 6: ...supply It is not recommended to leave any heating apparatus unattended during operation Only use Original Equipment manufacture s spares and accessories Ref Section 11 Page 5 of 24 M6493 Issue 10 3 En...

Page 7: ...s cord and moulded IEC plug and lead set May be different from illustration CN 200D Digital Controller Instruction Book Wall fixing Bkt x 1 and screws x 2 per bag Temperature Probe 1 For future refere...

Page 8: ...hot 5 8 If the controller is to be used on a retort rod make sure it isn t positioned over any heating apparatus 5 9 If using the wall mounting bracket provided carefully mark and drill two suitable h...

Page 9: ...issues within the design and manufacturing process without compromising end product performance and value 6 2 Packaging materials have been selected such that they may be sorted for recycling 6 3 At...

Page 10: ...te label and ensure your mains electrical supply voltage is compatible with this product Page 10 of 24 M6493 Issue 10 3 7 PRODUCT OPERATION 7 1 The CN 200D controller has been designed for easy operat...

Page 11: ...vely large and the heater will cause overshoot and wide variations in temperature 11 Page 11 of 24 M6493 Issue 10 3 7 2 Connection 7 2 1 Plug in the temperature probe to the 5 pin DIN socket Place the...

Page 12: ...ller This is achieved using the integrative action time and integrative action reset A derivative function can be combined with the proportional controller to provide the controller with the ability t...

Page 13: ...is a dual function value of the selected parameter when in the it is used to display the S 7 4 4 The is an Exit Stand by b or off 7 5 Operating Modes 7 5 1 The MB810B has two modes of oper mode The u...

Page 14: ...is used to increase the the display or to scroll through the paramete 7 4 2 The key is used to decrease th the display or to scroll through the paramete 7 4 3 The key is a dual function key value of...

Page 15: ...d to decrease the value of the param the display or to scroll through the parameter menu 7 4 3 The key is a dual function key It is used to display value of the selected parameter when in Programming...

Page 16: ...always off the next parameter will be ATM THR output programmed for second thermostat control the next parameter will be 2SM AL0 contacts open when an alarm condition occurs the next parameter will be...

Page 17: ...19 9 RHI Maximum range values RLO takes the maximum value measured by the transmitter i e the value matching 1V 20mA RHI RLO 99 9 Maximum range values RHI takes the maximum value measured by the trans...

Page 18: ...re earthed ground 2 meters long Moulded IEC plug and Lead set supply cord SJT VW 1 Replace only with equivalent cable Lead set plug fuse UK only 13A BSEN1362 Mains Output Non detachable 3 core mains c...

Page 19: ...remove it from the mains supply Open fuse draw and remove fuses Fit replacement fuses and close the draw 9 MAINTENANCE 9 1 General Information Unplug the unit from the mains voltage supply before und...

Page 20: ...is used to increase the value of the parameter shown on the display or to scroll through the parameter menu 7 4 2 The key is used to decrease the value of the parameter shown on the display or to scr...

Page 21: ...tact your local sales specialist or email cpspares antylia com to enquire about available spares Please visit www Cole Parmer com for a full list of available accessories 11 CUSTOMER AND TECHNICAL SUP...

Page 22: ...22 12 NOTES...

Page 23: ...o we cannot guarantee that interference will not occur in practise Where there is a possibility that injury damage or loss might occur if equipment malfunctions due to radio frequency interference or...

Page 24: ...tylia com W coleparmer fr Italy T 39 0 284349215 E it sales antylia com W coleparmer it India T 9122 61394444 E info coleparmer in W coleparmer in China T 1 847 549 7600 E sales antylia com W coleparm...

Reviews: