Figure 16: Keys and indications used for testing of the detection elements
9.2.2. Test of detectors and manual call points in the system
In order to test that the detectors and manual call points of the system are working properly, the
following operations must be carried out:
1) Place the zone in test mode (see chapter 9.2.1).
2) Test the detector/manual call point. The control panel must go into alarm mode
activating indication leds “A” and “P” of the zone.
Note: The general sounder indicator led “F” will activate when its configured delay
time has passed.
Note: The indicator led “P” activates fixe or flashes depending on whether or not the
alarm is triggered by a manual call point or a detector respectively.
3) After some 20 seconds, the control panel will restart automatically to continue with the
following test.
4) Repeat operations 2 and 3 until all the necessary detectors and manual call points
have been tested.
5) Disable the test mode for that zone.
6) Repeat operations 1 to 5 for all the zones that may need it.