background image

4

SYNCHRONISATION

SWITCHMATIC 2T can be synchronized to another unit SWITCHMATIC 2T 

managing and protecting 2 pumps operating in cascade with alternated 

starting sequence. Next steps must be followed:

1. GO TO ADVANCED MENU:   +   +   

- In 

step 2

: select E01 in a unit (this one will be the master) and select E02 

in the other unit (this one will be the slave). 

- In 

step 3

: select 

identical

 parameters of gap between pressures d.XX. 

This is the difference beetween the starting pressure of main and au

-

xiliary pumps, it is also the difference beetween stop pressures of both 

pumps.

2. Press   repeatedly until exit the ADVANCED MENU.

3. SET 

identical

 cut-in and cut-out pressures in both units.

To optimize the synchronization, the minimum difference between 

the start and stop pressures must be at least 1 bar.

4. Press   in order to disable the units. Is displayed “OFF”.
5. Press 

 

again in both units in order to activate the synchronization.

Remark 4: after 10 cycles the unit configured E01 will display pressu

-

re and the unit configured E02 will display current in Amps.  

PRESSURE SENSOR CALIBRATION

In case of wrong lecture of the pressure sensor it can be adjusted again. 

For the pressure sensor calibration is necessary to have a pressure gauge 

in the installation. Proceed following next steps:

ZERO REGULATION
1.  Press ENTER    to disconnect the device. It ill be displayed OFF.

2.  Open the taps living the hydraulic net without pressure.
3.  Press simultaneously the buttons   and   until the display show 0.0 

flashing.

4.  Press     to validate. 

FULL SCALE

1.  Start the pump until cut-out of the pressure switch.
2.  Press simultaneously the buttons    and 

 till the display flashes with 

a figure.

3.  Adjust the pressure with the arrows push-buttons to  get the pressure de-

sired.

4.  Press     to validate. 

Remark 5: pressure sensor decalibration should not be a normal 

event. If it is frequently repeated contact the technical service.  

WARNINGS AND ALARMS

COD.

DESCRIPTION

SYSTEM REACTION

A01

O

DRY-RUNNING

When is detected a dry-run operation the 

pump is automatically stopped. By mean 

of ENTER the normal operation can be 

manually restored.

( ( O ) )

After the activation of the dry-running 

alarm if the Automatic system reset (ART) 

is enabled, a first attempt at 5 minutes and 

then an attempt every 30 minutes for 24 

hours is performed in order to restore the 

normal operation. This alarm can also be 

reset manually with the ENTER push-but-

ton. If the alarm persists after 24 h we find 

a definitive alarm. 

A11

O

DRY-RUNNING 

(BY MINIMUM 

PRESSURE)

Is displayed during normal operation if the 

pressure is below the minimum pressure 

(Px.x) - previously set - during a period 

(txx) - also previously set - in the ADVAN-

CED MENU.

If at any time the pressure exceeds the mi-

nimum pressure, the operation is restored 

automatically and the alarm is cleared.

Normal operation can also be restored 

manually by pressing ENTER.

A02

OVERLOAD

Overcurrent alarm is activated when the 

nominal pump current is exceeded. 

4 automatic reset attempts prior to the 

final alarm are performed.

During the attempts display will show 

current.

Normal operation can also be restored 

manually by pressing ENTER.

( ( O ) )

A04

(((O)))

FAST CYCLING

This alarm can be unabled or activated in 

the BASIC MENU.  The alarm is activated 

when 3 consecutive cycles occur in a range 

lower than the set time (between cycle and 

cycle). 

If it has been activated rc1, this alarm does 

not stop the normal operation but are 

added 5 seconds to the start delay in order 

to protect the electric pump.

If it has been activated rc2, the pump is 

stopped.

To RESET the normal operation press 

ENTER.

A05

O

DAMAGED PRES-

SURE TRANS-

MITTER

CONTACT WITH YOUR SUPPLIER.

A08

O

OVERVOLTAGE

Overvoltage alarm is activated when the 

power supply voltage is exceeded. 

4 automatic reset attempts prior to the 

final alarm are performed.

During the attempts display will show .

Normal operation can also be restored 

manually by pressing ENTER.

( ( O ) )

A09

O

UNDERVOLTAGE

Undervoltage alarm is activated when 

the power supply voltageis under the 

minimum. 

4 automatic reset attempts prior to the 

final alarm are performed.

During the attempts display will show .

Normal operation can also be restored 

manually by pressing ENTER.

( ( O ) )

EC STAMENT OF COMPLIANCE 

COELBO CONTROL SYSTEM, S.L. 

States, on our own responsibility, that all materials here with related 

comply with the following European Directives: 2014/35/EU. 2014/30/EU. 

2011/65/EU. 

Name:   - SWITCHMATIC 2T

 

Standards : EN-60730-2-6, EN-60730-1, EN-61000-6-1, EN-61000-6-3, IEC-

60730-1, IEC-60730-2-6

F. Roldán Cazorla

Director Técnico

04/05/2016

Reviews: