background image

3

P-BUTTON

TOUCH

ACTION

click!

From state ON

: unit OFF.

From state OFF

: the pump starts and keeps opera-

ting until reaching Pstop.

From any configuration MENU

: the parameter 

value is accepted.

HOLD 

DOWN

From state ON

: unit OFF.

From state OFF

: the pump starts and keeps opera-

ting until the push-button is released.

click!

Pstart is displayed on the screen for 3 seconds.

3”

Pstart adjustment mode.

click!

Pstop is displayed on the screen for 3 seconds.

3”

Pstop adjustment mode.

click!

Is displayed on the screen instantaneous current 

consumption. 

If it is already displayed then we switch to instanta-

neous pressure view.

3”

Rated current adjustment.

click!

Is displayed on the screen instantaneous voltage.

If it is already displayed then we switch to instanta-

neous pressure view.

3”

Adjust rated voltage between different options: 

110V, 125V, 220V, 230V, 380V, 400V.

STARTUP 

 

Before starting the device please read the previous sections, espe-

cially “Hydraulic Installation” and “Electrical connection”.

Follow next steps:

1. Set the power supply voltage.

- Press

during 3 seconds.

- The voltage value is displayed on screen, LED V lights up and display 

is flashing. 

- By mean of   and   is adjusted the power supply voltage. See 

Note 1.

- Press   for validation.

2. Set the pump rated current intensity value.

- Press    during 3 seconds.

- The current intensity value is displayed on screen, LED A lights up and 

display is flashing. 

- By mean of   and 

 is adjusted the rated current reflected in the 

characteristics plate of the motor. See Note 2.

- Press   for validation.

3. Start the device by pressing  .

4. Set the cut-in (start) pressure:

- Press    during 3 seconds.

- The start pressure value is displayed on screen, LED START lights up 

and display is flashing.  

- By mean of   and   is adjusted the start pressure from 0,5 to 11,5 

bar 

(+ version=11 bar)

.

- Press   for validation.

5. Set the cut-out (stop) pressure:

-  Press   during 3 seconds.

-  The stop pressure value is displayed on screen, LED STOP lights up 

and display is flashing.  

- By mean of   and   is adjusted the stop pressure from 1 to 12 bar 

(+ version=12 bar)

.

- Press   for validation.

6. The unit is ready to operate but more optional adjustments can be set 

through basic and advanced MENUS. See the next chapter. 

Remark 1: it is important to introduce exactly the power supply 

voltage specified on the nameplate of the pump.

Remark 2: it is important to introduce exactly the rated current 

specified on the nameplate of the pump.

BASIC MENU 

  +   

- Press simultaneously   +   during 5 seconds.
- By mean of   or   the values can be changed.
- Press   for validation.

- The parameters sequence is:

it

TYPE

SYSTEM REACTION

FACTORY 

SETTING

1

BAR

P

We can select the pressure units displayed 

beetween bar and psi. 

bar

2

rc0

rc2

Fast-cycling alarm:

- rc0: alarm unabled.

- rc1: activated, when hammering is detected 

it is delayed the start in order to protect 

the pump.

- rc2: alarm is activated and the pump is stop-

ped upon detection.

rc2

3

r.01

r.99

Only if fast-cycling alarm has been activated in 

the previous step (rc1&rc2). It can be choosed 

the maximum time period between 3 consecu-

tive starts that will be considered fast cycling 

(between 1 sec. and 99 sec.)

3 se-

conds

4

Sb0

Sb1

Stand-by mode activated (Sb1), for low power 

consumption, or unabled (Sb0).

Sb0

ADVANCED MENU  

 +   + 

- Press simultaneously  +   +   during 5 seconds.
- By mean of   or   the values can be changed.
- Press   for validation.

- The parameters sequence is:

it

TYPE

SYSTEM REACTION

FACTORY 

SETTING

1

nc

no

Select the operation MODE as a conventio-

nal pressure switch (nc = normally closed) or 

reverse (no = normally open). *see remark 3

nc

2

E00

E01/02

Select the operation mode Individual (E00) 

or Master/Slave (E01/E02) in case of be 

assembled in groups of two pumps. 

E00

2.1

d.05

d.1

Sets the minimum gap between Pstart 1 and 

Pstart 2 and/or Pstop 1 and Pstop 2.

d.05

3

ct0

ct9

Sets a time delay between 0 and 9 seconds 

to the start (is not available in synchronized 

operation mode).

ct0

4

dt0

dt9

Sets a time delay between 0 and 9 seconds 

to the stop.

dt0

5

Ar0

Ar1

Activation of the automatic restore system 

ART (Ar1) o disable (Ar0).

Ar0

6

P0.0

Px.x

It allows setting a minimum operating 

pressure under which the device would 

determine dry-running operation. 

 0 bar

0 psi

6.1

t05

t99

Set the time period between 5 and 99 

seconds below the minimum operating 

pressure that will be considered a dry-

running operation.

20”

7

c10

c30

It allows setting a % of nominal current 

above which the device will activate the 

overcurrent protection.

c20

8

rS0

rS1

If we change rS0 to rS1 and push ENTER 

default values are restored.

rS0

Remark 3:

By choosing “no” (normally open) it will operate as an auxiliary 

pressure control element in the suction of the pump. It will restart 

when the suction pressure reaches the configured PStart.

Example: 

- PStop:   0,9 bar

- PStart:  1,2 bar