SAFETY, INSTALLATION AND OPERATION MANUAL

AVANCIS POWERMAX

®

PHOTOVOLTAIC MODULES

Fire Safety

• Follow the local guidelines, codes and

requirements for fire safety.

• The  installation  of  a  PV  system  on  a

build ing  may  affect  fire  safety  of  the
building.

• For  roof  application,  the  PV  system

must be mounted over a fire-resistant
roof covering rated for the application
(outside USA and Canada).

• Do not install or use PowerMax

®

mod-

ules  near  hazardous  locations  where
flam mable gases or vapors can be gen-
erated or collected.

• PowerMax

®

modules mounted on build -

ings will continue to produce hazardous
DC voltage in case of a fire, even in the
following cases:
• low-light intensity 
• disconnected line between PV mod-

ules and inverter

• partly or entirely damaged modules
• damaged DC cabling

• Stay  away  from  the  PV  sytem  during

and after a fire.

• Inform the fire fighters about the par-

ticular hazards from the PV system.

• After the fire, have your installer bring the

PV system in a safe mode (if possible).

Mechanical Installation

• Depending on the installation, appro-

priate measures should be taken to pre-
vent any water, dirt or other substances
from accumulating on the module.

• Landscape and portrait mounting of the

modules in different directions is allowed.
All modules should be mounted in one
direction to achieve a unique appealing
surface. This means that the module la-
bels on the backsides are pointing to the
same side.

• PowerMax

®

modules must be securely

fastened  using  support  frames  or
mount ing kits suitable for PV applica-
tions and designed for local maximum
wind  and  snow  loads.  Follow  the  in-
structions from the applicable suppliers.

• Ensure  that  PowerMax

®

modules  are

not subjected to wind or snow loads in
excess  of  the  maximum  permissible
loads  as  specified  on  the  applicable
PowerMax

®

Product Information litera-

ture.

• When necessary, fix two to four hooks

per Power Max

®

module at the mount-

ing area in the back rail in order to pre-
vent the glass sliding down. The end of
these hooks should go around the glass
edge without touching it. When allowed,
alternative measures may be used as well.

• Ensure  that  PowerMax®  modules  are

not subjected to excessive forces due to
thermal  expansion  of  the  support
 structure.

• During installation and operation, the

support structure must not cause exces-
sive bending or twisting of the Power-
Max

®

module.

• Provide adequate rear ventilation under

a PowerMax

®

module for cooling and

dissipation of condensation or moisture.

• When  mounted,  clearance  of  5  mm

 between  PowerMax

®

modules  is  re-

quired to allow for thermal expansion
of the modules.

• With the exception of the back rails, all

other parts of the PowerMax

®

modules

must  always  be  kept  free  from  any
structural elements that can come into
contact  with  the  module  and  cause
damage.

• Do not drill any additional holes in the

back rails. Doing so could compromise
the mechanical inte g rity of the Power-
Max

®

module  and/or  cause  electrical

hazards or corrosion.

• AVANCIS requires that its PowerMax

®

modules  are  mounted  using  the  four
mounting areas locat ed on the back rails
(also see the drawings).

• The modules' glass edges are sensitive

to  impact.  Avoid  contact  with  other
modules, tools, etc.

Electrical Installation

• PV modules of different configurations

and  different  nominal  power  ratings
must not be used in the same PV array,
unless the inverters are specified for this.

• PowerMax

®

modules are factory-equipped

with  electrical  cables  and  connectors
for easy interconnection in series.

• Use  identical  LC4  connectors  for

connec ting  the  PV  modules.  In  case
connectors of different manufacturers
are to be paired, the connection should
be approved in writing by both manu-
facturers.

• User-supplied electrical cable extensions

might be required for connecting the
PowerMax

®

modules.

• Use  applicable  system  wiring  with

 suitable  cross-sectional  areas  and
 connectors  that  are  approved  for  the
maximum  reverse  current  (I

r

)  of  the

 PowerMax

®

module.

• Match the polarities of electrical cables

and  terminals  when  making  the  con-
nections; failure to do so may result in
damage to the PowerMax

®

module.

• Make sure that the PV system has ap-

propiate lightning and over-voltage pro-
tection and follow any applicable regu-
lations (including those from insurance
companies).

• Ensure that all electrical connections are

secure and tight.

• A bypass-diode is integrated in one of 

the  two  PowerMax

®

module  junction

boxes.  This  diode  is  not  user-replace-
able.  The  junction  box  must  not  be
opened.

• The maximum number of PowerMax

®

modules being connected in series must
be calculated in line with the applicable
regulations in such a way that the speci -
fied maximum system voltage (V

sys

) of

the PowerMax

®

module and all other

electrical  DC  components  will  not  be
exceeded  in  open-circuit  operation,
even at low temperatures. If there are n
modules,  the  following  must  apply:
n*U

oc

< U

sys

.

• Not more than two PowerMax

®

 modules

or module strings should be connected
in  parallel   without  using  appropriate
string current protection (otherwise the
maximum  I

r

specification  may  be  ex-

ceeded  and  the  module  will  be  dam-
aged).

Underwriters Laboratory Information for
USA and Canada:

• Refer to section 690-8 of the National

Electric Code (NEC) for an additional
multiplying  factor  of  125  %  which
may be applicable.

• Under normal conditions, PowerMax

®

modules are likely to experience con-
ditions  that  produce  more  current
and/or voltage than reported at Stan-
dard Test Conditions. Accordingly, the
values of I

sc

and V

oc

marked on this

module should be multiplied by a factor
of 1.25 resp. 1.10 when determining
component voltage ratings, conduc-
tor capacities, fuse sizes and size of
controls connected to the PV output.

14

©2015  |  AVANCIS GmbH  |  Solarstrasse 3  |  04860 Torgau  |  Germany  |  [email protected]  |  www.avancis.de  |  May 2015

Summary of Contents for AVANCIS POWERMAX 3.5

Page 1: ...AVANCIS POWERMAX PHOTOVOLTAIC MODULES SAFETY INSTALLATION AND OPERATION MANUAL DEUTSCH ENGLISH A CNBM COMPANY...

Page 2: ...2...

Page 3: ...is de May 2015 3 INHALT CONTENT Deutsch Seite 5 AVANCIS POWERMAX PHOTOVOLTAIK MODULE SICHERHEITS INSTALLATIONS UND BETRIEBSHANDBUCH English Page 11 AVANCIS POWERMAX PHOTOVOLTAIC MODULES SAFETY INSTALL...

Page 4: ...2015 AVANCIS GmbH Solarstrasse 3 04860 Torgau Germany service avancis de www avancis de May 2015 4...

Page 5: ...AVANCIS POWERMAX PHOTOVOLTAIK MODULE SICHERHEITS INSTALLATIONS UND BETRIEBSHANDBUCH DEUTSCH A CNBM COMPANY...

Page 6: ...Max Module sind bei Verdacht auf Probleme von einem Fachmann vom PV System abzuh ngen und zur Inspektion und anschlie enden Ma nahmen gem Beschreibung in AVANCIS EINGE SCHR NKTER GARANTIE F R PV MODUL...

Page 7: ...hnet Hinsichtlich des Recyclings in Ihrer Region siehe www epsrecycling org Treten Sie niemals auf die Modulver packungen oder auf die PowerMax Module und achten Sie darauf dass keine Gegenst nde auf...

Page 8: ...ets frei von Konstruktions elementen sein die mit dem Modul in Ber hrung kommen und Sch den ver ursachen k nnen Bohren Sie keine zus tzlichen L cher in die R ckenschienen Dies k nnte die mechanische I...

Page 9: ...geltenden Regelungen Vorschriften und Normen erf llen Schraube Mutter Zahnscheibe R ckenschiene Zahnscheibe Erdungskabel Montage PowerMax Module m ssen mit Hilfe der vier Stahlklemmen mit einer Be sch...

Page 10: ...l keinen zu hohen Temperaturschwankungen ausgesetzt ist Haftungsausschluss Da die Einhaltung der Anweisungen die ses Sicherheits Installations und Be triebshandbuches und die Bedingungen und Verfahren...

Page 11: ...AVANCIS POWERMAX PHOTOVOLTAIC MODULES SAFETY INSTALLATION AND OPERATION MANUAL ENGLISH A CNBM COMPANY...

Page 12: ...modules with a suspected problem should be removed from the PV system by a qualified person and be re turned to AVANCIS for inspection and subsequent actions as described in the AVANCIS LIMITED WARRAN...

Page 13: ...ease visit www epsrecycling org Do not stand or step on the module boxes or on the PowerMax modules and prevent objects from falling on the modules Do not drop PowerMax modules and avoid setting the m...

Page 14: ...not drill any additional holes in the back rails Doing so could compromise the mechanical integrity of the Power Max module and or cause electrical hazards or corrosion AVANCIS requires that its Power...

Page 15: ...long as they meet the applicable regulations code requirements and standards Mounting PowerMax modules should be fastened using four steel clamps with a minimum coating as described in the AVANCIS cla...

Page 16: ...der any patent or patent rights The information provided in this Safety Installation and Operation Manual including product specifications without limitations and suggestions do not constitute a warra...

Page 17: ...AVANCIS POWERMAX A CNBM COMPANY...

Page 18: ...rstra e 3 04860 Torgau service avancis de www avancis de 2015 5 AVANCIS POWERMAX AVANCIS PowerMax AVANCIS AVANCIS 19 19 19 20 20 20 PowerMax 21 21 10 kWh m AVANCIS PowerMax 22 22 22 AVANCIS PowerMax D...

Page 19: ...erMax PowerMax AVANCIS PowerMax AVANCIS Power Max EPS EPS www epsrecycling org Power Max PowerMax PowerMax PowerMax PowerMax PowerMax PowerMax PowerMax PowerMax PowerMax AVANCIS PowerMax PowerMax Powe...

Page 20: ...PowerMax PowerMax AVANCIS PowerMax PowerMax LC4 PowerMax PowerMax Ir PowerMax PowerMax PowerMax PowerMax Usys n n Uoc Usys 2 Power Max Ir Underwriters Laboratory NEC 690 8 125 PowerMax Isc Uoc 1 25 1...

Page 21: ...ANCIS PowerMax PowerMax AVANCIS 0 42 cm 0 17 M4 PowerMax 4 AVANCIS 2 PowerMax AVANCIS AVANCIS www avancis de AVANCIS 2015 AVANCIS Solarstra e 3 04860 Torgau service avancis de www avancis de 2015 5 AV...

Page 22: ...PowerMax AVANCIS PowerMax AVANCIS GmbH Solarstra e 3 04860 Torgau 49 0 3421 7388 0 49 0 3421 7388 111 service avancis de www avancis de 10 kWh m AVANCIS PowerMax 1000 W m 25 C 1 5 mpp PowerMax 120 12...

Page 23: ...23...

Page 24: ...ch bitte an In case of questions please contact AVANCIS GmbH Solarstra e 3 04860 Torgau Germany Telefon 49 0 3421 7388 0 Fax 49 0 3421 7388 111 service avancis de www avancis de Mat Nr 2010170 G ltig...

Reviews: