background image

www.cmp-products.com

www.cmp-products.com

INSTALLATION INSTRUCTIONS FOR CMP CABLE UNION PX780REX

UNION COMPONENTS - It is not necessary to dismantle the union any further than illustrated below

1. Entry Item

2. Serrated Flamepath

3. Nut

4. Conduit Connector

5. Washer

6. Resin Dam

7. Compound Tube

8. Thread Shield

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION

1. Prepare the cable by removing the outer sheath from the cores so that they are exposed within
the Compound Tube when finally assembled.

1

2

3

4

NOTE: THERE IS NO NEED TO DISSASSEMBLE THE UNION

3. Feed the cables/cores through the union.

If the installation uses only cores (i.e. no cable sheath) then
electrical tape must be wrapped around the cores at the position
at which it will engage the resin dam.

Use the length of the union as a guide to position the tape as
shown above (guide length “L”)

5

6

7

8

2. Remove any bedding or fillers from around the cable cores. If the cable cores have screens,
these should be unwound and then twisted together to form a single core.
This single core and/or any drain wires present should be sleeved with some heat shrink tubing.

Electrical tape MUST be wrapped around the tips of the
cable cores. This is to ensure the cable cores are
together and also to cover any sharp edges that could
potentially tear the Resin Dam during installation.

L

4. Mix the Resin and apply as per RapidEx instructions.

5.1 When the Resin has cured the Entry Item (1) should be removed from the assembly and fully tightened into the 
apparatus. 

5.2 Tighten the Conduit Connector (4) onto the conduit and then tighten to the Entry Item (1) using the Nut (3) to 
complete the installation.