background image

M0V940M13-06 WSN-XIN 

21-141 

41

8.18  Remote control - option

The keyboard repeats all the built-in control functions.

For details see:

8 Control p. 31

8.19  Ambient temperature display

It is possible to set the keypad to display the ambient temperature.

The probe is not used to perform the ambient thermoregulation.

Follow these steps:

Step

Display

Action

Keys

Menu/Variable

Notes

1

Main menu

Press

PAr

2

PAr

Press

PAr

3

PAr

Select

Cr

4

Cr

Press

Cr..

5

Cr..

Select

Cr00
Anable ambient probe

6

Cr00

Confirm

0

7

0

Select

2

8

2

Confirm

2

9

Press

Back to the previous menu

10

Select

Cr30
Temperature display

11

Cr30

Confirm

0

12

0

Select

16

13

16

Confirm

14

Press

Back to the previous menu

Summary of Contents for WSN-XIN 101

Page 1: ...M0V940M13 06 13 09 16 Installation and operating manual Air heat pump ductable water for indoor installation WSN XIN 21 141...

Page 2: ...he installation and maintenance cost for the life cycle of the system The purpose of this manual is to provide you with information that is useful from reception of the equipment through installation...

Page 3: ...uide 5 2 General description 6 3 Reception 8 4 Positioning 10 5 Water connections 14 6 Electrical connections 16 7 Start up 23 8 Control 31 9 Maintenance 45 10 Accessories 49 11 Decommissioning 62 12...

Page 4: ...4 WSN XIN 21 141 M0V940M13 06...

Page 5: ...agement p 56 G 2 setpoint control 2 setpoint 1 setpoint 10 5 Boiler management p 56 H BUS connection H H1 100mt max 10 5 Boiler management p 56 I ON OFF 6 7 SA1 On Off Standby remote p 21 L summer win...

Page 6: ...rsonnel they may cause damages to things and injuries people 2 4 Intended use Use the unit only for cooling heating water or a water and glycol mix for air conditioning only keep to the limits foresee...

Page 7: ...case of breakdown or malfunction Immediately deactivate the unit Contact a service centre authorized by the manufacturer The installer must train the user particularly on Start up shutdown Set points...

Page 8: ...ance clear evidence of deficiencies damages during transport Contact by fax and registered mail with advice of receipt to supplier and the carrier Any disputes must be made within 8 days from the date...

Page 9: ...1 141 9 B Screws 3 3 Packaging removing Be careful not to damage the unit Keep packing material out of children s reach it may be dangerous Recycle and dispose of the packaging material in conformity...

Page 10: ...ust Avoid installations in places subject to flooding verify unit weight and bearing point capacity verify that all bearing points are aligned and leveled install the unit raised from the ground max d...

Page 11: ...unit coil B Keep the min distances from the podestrian areas C Avoid the by pass between the two air flows D Avoid snow accumulations on batteries E Avoid the rain input F Avoid the angle curves and...

Page 12: ...ndensate water When a heat pump is running it produces a considerable amount of water due to the defrosting cycles of the external coil The condensation must be eliminated in a manner to avoid wetting...

Page 13: ...M0V940M13 06 WSN XIN 21 141 13 4 5 GMX Supply grille Accessory Fix the grille with the screws...

Page 14: ...ol or safeguard the pipes with heating cables placed under the insulation or empty the system in cases of long non use 5 3 Anti freeze solution The use of an anti freeze solution results in an increas...

Page 15: ...entions and at worst cases can cause damages to the exchangers and the other parts 5 7 Recommended connection The installer must define component type position in system 2 7 9 13 3 1 14 UNIT 6 10 12 4...

Page 16: ...mum admitted conditions F L I full load input full load power input at max admissible condition Electrical wiringdiagram Nr If the DHW module is present consider the electric resistance absorption in...

Page 17: ...6 4 Power input A mm 22 B mm 22 C mm 34 Install the isolator switch near the unit Fix the cables if vacated may be subject to tearing The cable must not touch the compressor and the refrigerant pipin...

Page 18: ...le FU1 Fuse AP2 Electronic thermostatic management FU2 230V aux cicuit fuse AP4 Fan control module KA1 Inverter alarm auxiliary relay AP6 RS 485 module OPTIONAL KA2 Compressor control relay C1 C2 Fan...

Page 19: ...485 module OPTIONAL FU2 compressor overload protection and timer T1 Transformer QS1 Main isolator switch FU1 compressor overload protection and timer Size 51 71 QM1 Compressor line protection FU2 230V...

Page 20: ...inter 6 8 SA2 Summer Winter remote p 22 3 Only for sizes 21 41 SA3 Second setpoint enabling Ref p 4 Only for sizes 51 71 M8 Pump use Provided by the customer A Fuses Provided by the customer XT1 Termi...

Page 21: ...winter YVc 3 way Boiler valve 6 7 SA1 On Off Standby remote Set parameter CL43 Keys Esc Set Menu PAr Menu CL CL43 ON OFF Standby Time bands only DHW 2 SA1 ON OFF remote from keypad key DOWN YES from...

Page 22: ...d disabled SUMMER WINTER 6 9 SA3 Second setpoint enabling switch For details see 7 10 SA3 2 set point p 25 6 10 Remote control For details see 10 Accessories p 49 6 11 Domestic hot water module For de...

Page 23: ...return and supply no bypass no stratification 4 structure integrity 5 fans run freely 6 unit on vibration isolators 7 unit input water filter shut off valves for cleaning 8 vibration isolators on wate...

Page 24: ...freeze solutions make sure the glycol percentage is suitable for the type of use envisaged Weight of glycol 10 20 30 40 Freezing temperature C 3 9 8 9 15 6 23 4 Safety temperature C 1 4 10 19 Modify t...

Page 25: ...that the air and water temperatures are within in the operating limits Start up the unit With unit operating in stable conditions check Voltage Total absorption of the unit Absorption of the single el...

Page 26: ...ompensated setpoint 14 C Cool Description Example dS01 Temperature controller dynamic differential proportional band in Cool dS01 6 C dS03 Maximum temperature controller dynamic differential in Cool d...

Page 27: ...value 2 set par PI31 PI30 3 note down the PI41 value 4 set par PI41 PI40 5 if the E020 alarm appears proceed from section 8 6 if the E020 alarm does not appear proceed from section 10 7 reset the ala...

Page 28: ...on is enabled by default To deactivate the funcion PI22 0 Heat pump Off Pi22 ON Pi22 pump ON Off Pi03 7 16 Circulating pump anti lock function The function prevents mechanical locks of the circulation...

Page 29: ...lating pump for antifreeze 5 C PI52 hysteresis 2 C The function is enabled by default To deactivate the funcion PI50 0 pump Off Pi52 ON Pi51 t H2O inlet 7 18 Antifreeze function with heater HI12 heate...

Page 30: ...the different fluids water air both in input and in output from the unit temperature and pressures on the characteristic points of the refrigerating circuit compressor discharge liquid intake The mea...

Page 31: ...d to scheduling Defrosting Automatic Manual defrosting activated ON Domestic hot water Flashing D H W mode standby not used currently Boiler activation request Heater ON D H W Water set point compensa...

Page 32: ...nfiguration Fnc functions dEF manual defrosting tA alarm reset St on off CC copy card EUr alarm log reset PASS password EU alarms Alarm log Manual defrosting possible only under certain conditions Use...

Page 33: ...oint modification Step Display Action Keys Menu Variable Notes 1 Main menu Press Ai 2 Ai Select SP 3 SP Access Cool 4 Cool Select Choose Cool Heat AS 5 AS Confirm 50 6 50 Press Set the value 55 7 55 C...

Page 34: ...e resetting an alarm identify and remove its cause Repeated resets can cause irreversible damage Step Display Action Keys Menu Variable Notes 1 Er01 The alarm code is flashing 2 13 5 C Alternated to t...

Page 35: ...g an alarm identify and remove its cause Repeated resets can cause irreversible damage Step Display Action Keys Menu Variable Notes 1 Main menu Press PAr 2 PAr Select EU 3 EU Press Last registered ala...

Page 36: ...n Remote terminal Remote terminal I O Configuration CF ConFiguration Configuration Ui User interface User interface tr thermoregulation Thermoregulation St Stati Operating modes Operating stata CP Com...

Page 37: ...Event minutes par tE25 Unit mode par tE26 0 On 1 standby Cooling temperature par tE27 Heating temperature par tE28 DHW temperature par tE29 tE52 tE53 tE54 tE55 tE56 tE57 tE80 tE81 tE82 tE83 tE84 tE85...

Page 38: ...active scheduling A manual modification of the heat setpoint key Set SP menu Heat B manual modification of the heat setpoint key Set SP menu Heat C manual modification of the DHW setpoint key Set SP m...

Page 39: ...26 tE54 tE82 Cooling temperature tE27 tE55 tE83 Heating temperature tE28 tE56 tE84 DHW temperature tE29 tE57 tE85 Event 4 Time tE31 tE59 tE87 Minutes tE32 tE60 tE88 Mode 0 on 1 standby tE33 tE61 tE89...

Page 40: ...et point AS04 DHW hysteresis The scheduling can be programmed for each day of the week In the following example the antilegionella cycle is scheduled Wednesday duration 1 starting at 23 00 Sunday dura...

Page 41: ...mperature The probe is not used to perform the ambient thermoregulation Follow these steps Step Display Action Keys Menu Variable Notes 1 Main menu Press PAr 2 PAr Press PAr 3 PAr Select Cr 4 Cr Press...

Page 42: ...ress Ui 5 Ui Select Ui22 6 Ui22 Confirm 0 7 0 Select 1 8 1 Confirm 1 9 Press Back to the previous menu Step Display Action Keys Menu Variable Notes 1 Main menu Press 3 sec 2 Select Air1 3 Air1 Press I...

Page 43: ...O E066 Faulty DHW temperature probe AUTO E068 Faulty external temperature probe AUTO E069 Faulty high pressure input circuit AUTO E070 Faulty low pressure input circuit E071 Faulty compressor discharg...

Page 44: ...thermostatic sensor on the driver of di L1 High pressure di L2 Compressor Alarm di L3 Flow user side di L4 Remote On Off di L5 Remote Heat Cool AO AO L1 Primary pump it is a digital 0 1 AO L2 Fan sig...

Page 45: ...t is recommended to plan inspections at shorter intervals frequent use continuous or very intermittent use near the operating limits etc critical use service necessary 9 3 Unit booklet It s advisable...

Page 46: ...6 Air coil Contact with the exchanger fins can cause cuts wear protective gloves to perform the above described operations It is extremely important that the battery gives the maximum thermal exchang...

Page 47: ...pressor Compressor may stop Pumping With Motor Running Turn Off And Wait Until Cool May need More Than 1 Hour To Reset Advanced Scroll Temperature Protection 9 13 Condensate drain Dirt or scale can gi...

Page 48: ...48 WSN XIN 21 141 M0V940M13 06 Fan replacement...

Page 49: ...41 49 10 Accessories 10 1 Remote control QG Electrical panel XT1 Terminal block of the customer connections AP7 Room keypad A Max 100 mt Cable section Min 0 35 Max 1 mm2 LAN net A B 100 mt Max AMACSX...

Page 50: ...n Par CF01 protocol selection 0 Disabled 1 Modbus Parameter modification Connection of 1 between the unit and the system Parameter Description Range CF30 address Modbus 1 255 CF31 BaudRate Baud Rate 0...

Page 51: ...Domestic Hot Water by means of the temperature probe placed inside the storage tank The control allows the production of Domestic Hot Water to a specific set point that can be defined in 4 daily inte...

Page 52: ...ons we recommend you to store them in covered rooms and mild temperatures 15 20 C Storage tank type ACS300X ACS500X Suitable for heat pump Size 21 51 21 101 121 171 Pipe coil operating pressure bar 6...

Page 53: ...ration CMACSX The CMACSX module allows controlling the temperature of the Domestic Hot Water by means of the temperature probe placed inside the storage tank The control allows the production of Domes...

Page 54: ...and mild temperatures 15 20 C Storage tank type ACS3SX ACS5SX Suitable for heat pump Size 21 51 21 101 121 171 Upper and bottom coil operating pressure bar 6 6 Domestic hot water operating pressure b...

Page 55: ...eat pump BT7 DHW storage probe XT1 Terminal block of the customer connections R6 Electric heaters of the DHW storage provided by the Customer A LAN serial L max 100 mt Cable section Min 0 35 Max 1 mm2...

Page 56: ...stallation and DHW production The system configuration consists of 1 module to manage domestic hot water CMACSX 1 3 way diverting valve E between the heat pump and the auxiliary generator 1 3 way valv...

Page 57: ...o setting Keys Esc Set Menu PAr CL90 30 valve control of circuit boiler heat pump switching CL93 38 boiler start up control pi11 1 br00 3 br02 70 br03 0 1 br05 5 adjustable Setpoint heat pump operatio...

Page 58: ...block of the customer connections BT7 DHW storage probe A LAN serial L max 100 mt Cable section Min 0 35 Max 1 mm2 R6 Electric heaters of the DHW storage provided by the Customer YVACS 3DHWX 3 way val...

Page 59: ...5 1 5 2 Summer set point 2 SPCool 7 5 7 8 7 7 5 8 5 8 7 5 7 SCHEDULING EXAMPLE monday KA OFF Enabled set summer tuesday KA ON 2 Enabled set summer wednesday KA OFF Enabled set summer example summer s...

Page 60: ...60 WSN XIN 21 141 M0V940M13 06 10 7 Cabinet for Elfo Pool...

Page 61: ...M0V940M13 06 WSN XIN 21 141 61 1 Cooling operation with parameter r5 0 2 Heating operation with parameter r5 1...

Page 62: ...vered by the legislation in question are marked with the symbol on the side With the aim of protecting the environment all of our units are produced in compliance with Directive EC on waste electrical...

Page 63: ...eriodically check that all of the panels are correctly closed and fixed If there is a fire the temperature of the refrigerant could reach values that in crease the pressure to beyond the safety valve...

Page 64: ...14511 _2013 8 2 48 2 47 2 54 2 37 2 41 2 65 2 64 2 30 2 35 2 24 2 06 ESEER 12 3 41 3 25 3 36 3 04 3 30 4 27 4 33 4 12 3 92 3 58 3 43 Water flow rate 11 l s 0 19 0 25 0 29 0 42 0 56 0 74 0 80 0 93 1 15...

Page 65: ...to EN14511 2008 5 Entering leaving water temperature user side 40 45 C Entering external exchanger air temperature 7 C R H 85 6 Entering leaving water temperature user side 45 55 C Entering external e...

Page 66: ...ound pressure level Sound power level Octave band Hz 63 125 250 500 1000 2000 4000 8000 dB A dB A 100 21 88 77 69 65 64 66 60 41 44 59 100 31 95 87 76 71 69 66 62 48 45 69 100 41 97 89 77 72 70 68 64...

Page 67: ...nge where the use of ethylene glycol is mandatory in relation to the temperature of the water at the outlet of the user side exchanger 4 Operating range with modulating compressor Heating ELFOEnergy D...

Page 68: ...F 1 9 Condensate drain M Air supply Size 21 31 41 Length mm 1107 1107 1107 Depth mm 800 800 800 Height mm 988 988 988 W1 kg 35 35 35 W2 kg 39 2 39 2 39 2 W3 kg 40 40 40 W4 kg 24 24 24 Operating weight...

Page 69: ...F 1 9 Condensate drain M Supply Air Size 51 71 Length mm 1256 1256 Depth mm 834 834 Height mm 1234 1234 W1 kg 51 5 53 W2 kg 45 9 47 4 W3 kg 54 5 55 5 W4 kg 29 5 30 5 Operating weight kg 181 186 Shipp...

Page 70: ...ondensate drain M Air supply Size 81 91 101 Length mm 2016 2016 2016 Depth mm 1150 1150 1150 Height mm 1137 1137 1137 W1 kg 80 80 80 W2 kg 71 71 71 W3 kg 70 70 70 W4 kg 40 40 40 Operating weight kg 26...

Page 71: ...ondensate drain M Supply Air Size 121 131 141 Length mm 2016 2016 2016 Depth mm 1150 1150 1150 Height mm 1517 1517 1517 W1 kg 85 85 85 W2 kg 89 89 89 W3 kg 85 85 85 W4 kg 60 60 60 Operating weight kg...

Page 72: ...x 34 93 8855392 info clivetcomercial com CLIVET ESPA A S A U Service and Maintenance Division Calle Real de Burgos N 12 28860 Paracuellos del Jarama Madrid Espa a Tel 34 91 6658280 Fax 34 91 6657806 i...

Reviews: