M0V940M13-06 WSN-XIN
21-141
21
Electrical panel
sizes 81÷141 - 400/3/50
1
Unit
SA3
Second setpoint enabling
2
Connections perfomer by customer
AP7
Room keypad
A
Fuses
Provided by the customer
M8
Pump use
Provided by the customer
QS1
Isolating switch
XT1
Terminal block of the customer connections
QG
Electrical panel
Boiler
Boiler control, max 24v/AC
SA1
Remote ON-OFF
ALM
Cumulative fault signal,max 24v/AC
SA2
Remote summer/winter
YVc
3-way Boiler valve
6.7 SA1 = On-Off / Standby remote
Set parameter CL43:
Keys
Esc + Set
Menu PAr
Menu CL
CL43
ON/OFF
Standby
Time bands
only DHW
-2
SA1 = ON-OFF remote
from keypad: key DOWN
YES
from Menu: Operating mode
-1
from Menu: Fnc - St
SA1 = remote standby
NO
from Menu: Operating mode
0
from Menu: Fnc - St
from keypad: key DOWN
YES
from Menu: Operating mode
-28
from Menu: Fnc - St
from keypad: key DOWN
YES
SA1 = only Domestic Hot Water
remote*
OFF: emergency stop, not active the antifreeze safeties etc.
Standby: assisted stop, are active the antifreeze safeties etc.
* CL43= -28
Domestic hot water production even with OFF room thermostats