26
WSAT-XSC3 260.6-480.8
M08T40D16-02
If there are more units connected in a local network set the mode of operation.
MODE A
Every unit manages its own compressors according to the
setpoint.
Every unit optimizes its refrigeration circuits.
Pumps always active, even with compressor stoped.
P0658 = 0
P0657 > 0 °C
setpoint1 > setpoint2 > setpoint3
or
setpoint1 < setpoint2 < setpoint3
MODE B
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Pumps always active, even with compressor stoped.
P0658 = 1
P0657 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: optimal H2O temperature control
MODE C
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Active pumps only with active compressors.
P0658 = 2
P0657 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: minimum pumps consumption need balanced system (t1 = t2 = t3)
Path: Main Menu / Unit parameters / Master Slave
Parameters
Short description
Description
P0655
LNinstalledUnits
Number of network-connected units including the master
P0656
LNStandByUnits
Number of units kept in standby
P0657
LNOffset
Temperature Offset the master sum or subtract, depending on the way you set, in order of priority, to the set point of
the slave
P0658
TypeRegMS
Operation mode: 0=mode A; 1=mode B; 2=mode C
P0659
LNAddress
ProcessBus address unit
Summary of Contents for WSAT-XSC3 260.6-480.8
Page 46: ...46 WSAT XSC3 260 6 480 8 M08T40D16 02 8 16 Compressor replacement ...
Page 47: ...M08T40D16 02 WSAT XSC3 260 6 480 8 47 8 17 Exchanger replacement 8 18 Pump replacement ...
Page 49: ...M08T40D16 02 WSAT XSC3 260 6 480 8 49 ...
Page 50: ...50 WSAT XSC3 260 6 480 8 M08T40D16 02 ...
Page 75: ...Page intentionally left blank M08T40D16 02 WSAT XSC3 260 6 480 8 75 ...