Admissible water flow-rates
Minimum (Qmin) and maximum (Qmax) admissible water flow for the unit to operate correctly.
EXCELLENCE SC/EN
90.4
100.4
110.4
120.4
140.4
160.4
180.4
200.4
220.4
240.4
Qmin
[l/s]
8,0
8,0
9,3
9,3
10,1
11,5
14,3
14,3
16,4
16,4
Qmax
[l/s]
21,8
21,8
25,1
25,1
27,5
31,2
38,6
38,6
44,0
44,0
Overload and control device calibrations
open
closed
value
High pressure safety pressure switch
[kPa]
4050
3300
-
Antifreeze protection
[°C]
4
5.5
-
High pressure safety valve
[kPa]
-
-
4500
Low pressure safety valve
[kPa]
-
-
2950
Max no. of compressor starts per hour
[n°]
-
-
10
High compressor discharge temperature safety thermostat
[°C]
-
-
140
Exchanger operating range
Internal exchanger
DPr
DPw
PED (CE)
4500
4500
1000
DPr = Maximum operating pressure on refrigerant side in kPa
DPw = Maximum operating pressure on water side in kPa
5
WSAN-XSC3 90.4-240.4