WSAN-XSC3 90.4-240.4
11
4.6 Recommended connection
The installer must define:
•
component type
•
position in system
2
7
9
13
3
1
14
UNIT
6
10
12
4
5
8
15
F
11
1
antivibration joints
9
safety valve
2
piping support
10
Flow Switch
3
exchanger chemical cleaning bypass
11
pressure gauge
4
drain valve
12
thermometer
5
vent
13
filter
6
shut-off valve
14
Internal storage tank
7
Pump / circulating pump
15
Cleaning system bypass
8
expansion vessel
4.7 Hydraulic connections
•
take away the supplied connection union by acting on the connection joint
•
weld the union to the installation pipe
•
perform the connection between the installation pipe and the evaporator, using the joint
Do not weld the system pipe with the Victaulic connection joint attached.
The rubber gasket might be irreparably damaged.
4.8 Water filter
Use filter with mesh pitch:
1,6 mm
It must be installed immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The filter never should be removed, this operation invalidates the guaranty.
4.9 Flow Switch
The flow switch must be present to ensure shutdown of the unit if water is not circulating.
It has to be installed in a duct rectilinear part, not in proximity of curves that cause turbulences.
Electrically connect the flow switch at the inlet arranged on the XC terminal block.
The flow switch must be set to the minimum reachable flow rate.
A
!
A
A > 5 x Ø
Ø
B < A
A. minimum distance
B.
Summary of Contents for WSAN-XSC3 100.4
Page 44: ...44 WSAN XSC3 90 4 240 4 8 17 Compressor replacement ...
Page 45: ...WSAN XSC3 90 4 240 4 45 8 18 Exchanger replacement ...
Page 47: ...WSAN XSC3 90 4 240 4 47 ...
Page 48: ...48 WSAN XSC3 90 4 240 4 ...
Page 49: ...WSAN XSC3 90 4 240 4 49 ...
Page 63: ...Page intentionally left blank ...