M01Z40E12-03
WSA-XSC2 432-120D
49
code
description
detailed description
DO-687
Cumul.Alarm_Q2
Unit cumulative alarm status (N.0.Open=All OFF N.O. Closed=All ON): 0=Off 1=On
DO-687
CmdP1User_Q3
Command pump 1 utility side: 0=Off 1=On
DO-687
CmdP2User_Q4
Command pump 2 utility side: 0=Off 1=On
DO-687
CmdP3User_Q5
Command pump 3 utility side: 0=Off 1=On
DO-687
OpenYV FC_Q7
Opening control of the FREE-COOLING valve FC Closed = ON: 0=Off 1=On
DO-687
CloseYV FC_Q8
Closure control of the FREE-COOLING valve FC Closed = OFF: 0=Off 1=On
DO-687
AntifreezeHeater_Q6 Status of the control of the antifreeze heaters: 0=Off 1=On
S0001
StartsP1User
Number of startup totalized from Pump 1
S0002
StartsP2User
Number of startup totalized from Pump 2
S0003
StartsP3User
Number of startup totalized from Pump 3
S0004
Pump1 running hours Utilisation pump 1 hours
S0005
Pump2 running hours Utilisation pump 2 hours
S0006
Pump3 running hours Utilisation pump 3 hours
S0007
Antifreeze heat.
Antifreeze heater status 0=Off 1=On
S0008
Pump in antifreeze
Status of the utilisation pump for antifreeze protection 0=Off 1=On
S0009
Recovery
Recovery status: 0=Off 1=On
S0010
ActualSptTExt
Setpoint value calculated by the Text climate curve
S0011
ActualSptWR
Setpoint value calculated by the WaterReset function
S0012
StatusFREE-COOLING FREE-COOLING status 0=Off 1=On
S0013
GenWarning
0=Off 1=On
S0014
GenBlock
0=Off 1=On
S0015
NCompOnUnit
Number of compressors currently active on the machine
14.4 Circuit 1 status
code
description
detailed description
AI-94U
SuctionTemp_X2
Suction temperature
AI-94U
SuctionPressureX1
Low pressure transducer
AI-985
DischargeTC1_B1
Compressor 1 discharge temperature
AI-985
DischargeTC2_B2
Compressor 2 discharge temperature
AI-985
DischargeTC3_X2
Compressor 3 discharge temperature
AI-985
SourceTemp1_B3
Source 1 temperature (for machines with air-based sources and reversible on gas = Probe 1 on source battery.
For machines with water-based source = Source input probe)
AI-985
SourceTemp2_X1
Source 2 temperature (for machines with air-based sources and reversible on gas = Probe 2 on source battery.
For machines with water-based source = Source outlet probe)
AI-985
DischargePressure_X3 High pressure transducer
AO-985
%Cmd Cmp_X5
Percentage value of the status of the control signal of the modulating compressor
AO-985
%Cmd Source_X6
% value source modulating signal control
DI-985
Source WaterFlow_X4 Status of the source flow contact (Only active on machines with water-based source): 0=Fault 1=OK
DI-985
LP Pressure switch_X7 Status of the LP-pressure switch contact: 0=Fault 1=OK
DI-985
Ovl Inverter_DL1
Status of the inverter compressor heater contact: 0=Fault 1=OK
DI-985
HP Pressure switch_X8 Status of the HP-pressure switch contact: 0=Fault 1=OK
DI-985
Ovl Source_DL2
Status of the contact of the thermal protection of the source motors: 0=Fault 1=OK
DI-985
Ovl Cmp1_D1
Status of the contact of the thermal protection of compressor 1: 0=Fault 1=OK
DI-985
Ovl Cmp2_D2
Status of the contact of the thermal protection of compressor 2: 0=Fault 1=OK
DI-985
Ovl Cmp3_D3
Status of the contact of the thermal protection of compressor 3: 0=Fault 1=OK
DI-985
Diff.PressureOilS-
crew_D2
Status of the oil differential pressure switch contact (Active if compressor = Screw): 0=Fault 1=OK
DI-985
EnCircScrew_D3
Status of the circuit enabling input contact (Active if compressor = Screw): 0=Fault 1=OK
DO-985
Cmd Cmp1_Q2
Status of the compressor 1 control: 0=Off 1=On
DO-985
Cmd Cmp2_Q3
Status of the compressor 2 control: 0=Off 1=On
DO-985
Cmd Cmp3_Q4
Status of the compressor 3 control: 0=Off 1=On
DO-985
Cmd Source_Q1
Status of the source motor control: 0=Off 1=On
DO-985
Cmd Inj.Cmp1_Q5
Status of the compressor 1 liquid injection valve control: 0=Off 1=On
DO-985
Cmd Inj.Cmp2_Q7
Status of the compressor 2 liquid injection valve control: 0=Off 1=On