6.18 Water reset
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
The water reset correction affects the setpoint defined by the Climate curve TExt (actual setpoint).
The setpoint is shown at status S0011: ActualSptWR
Only if P0051: En WaterReset ≠ 0
Path: Main Menu / Unit parameters / Water reset
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Water reset
6
Water reset
Select
Parameter
7
Set
8
Confirm
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / Water reset
Parameters
Short description
Description
P0281:
MaxCWRC
Maximum correction to be applied to the setpoint
P0283:
SWRMaxC
Value of Water-Reset signal, where the variation of the Set Point, cooling, is maximum, i.e. equal to P0281
P0285
SWRMinC
Value of Water-Reset signal, where the variation of the Set Point, cooling, is minimal, i.e. equal to 0° C