M09G60E14-04
MSAT-XEE 8.2-30.2
39
14 Alarms - Status
14.1 Alarms
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Code
Description
Type
E000
Alarm phase monitor
AUTO
E001
High pressure (digital) circuit
*
E005
Low pressure (digital) circuit
*
E010
Compressor 1 Alarm
Manual
E011
Compressor 2 Alarm
Time
E041
Fan thermal
Manual
E045
Faulty clock error
AUTO
E046
Error: Clock to set
AUTO
E047
Error of LAN communication between main module and ambient keyboard (if present)
AUTO
E062
Faulty exchanger temperature probe
AUTO
E065
Faulty ambient keyboard temperature probe
AUTO
E069
Faulty high pressure input circuit
AUTO
E080
Configuration error
AUTO
E081
Signalling of compressor operating hour exceeding
Manual
E090
Signalling of alarm log record exceeding
Manual
A = AUTOMATIC reset
M = MANUAL reset
* after some interventions is necessary the manual reset
14.2 Status
Main menu→SET→Ai, di, AO, dO→Ai L1
Menu
Code
Description
Ai
AiE1
Not used
Ai L1
Fan thermal (0= input closed)
Ai L2
Phase monitor (0= input closed)
Ai L3
Not used
Ai L4
High pressure transducer
Ai L5
Not used
AiR1
ambient air temperature probe
Remote control
1Ai 1
Not used
1Ai 2
Not used
1Ai 3
Not used
of
di L1
High pressure
di L2
Low pressure switch
di L3
Compressor 1 line protection
di L4
Compressor 2 line protection
di L5
Compressor 1 request
diL6
Compressor 2 request
AO
AO L1
Not used
AO L2
Not used
AO L3
Fan signal
AO L4
Not used
AO L5
Not used