67
12 - TECHNICAL DATE
SOUND LEVELS - COOLING
SOUND POWER LEVEL (DB)
OCTAVE BAND (HZ)
Sound power level
Sound pressure
level
63 125 250 500 1000 2000 4000 8000
dB(A) dB(A)
125
27 25 37 40 34 30 29 30
34 47
150
28 26 38 40 35 31 30 31
35 48
210
31 32 38 41 42 36 30 26
37 50
270
32 34 41 42 45 41 37 27
41 54
320
36 38 45 46 49 45 41 31
45 58
[m
3
/h]
Sound levels are referred to unit at nominal condition when installed in false ceiling and connected to ducts. External static pressure 50 Pa.
Cooling: Ambient temperature 35°C D.B./ 24°C W.B., Extracted air temperature 27°C D.B./ 19°C W.B.
Average sound pressure level, according to UNIEN ISO 3744, is measured at 1m distance from the unit surface, when installed in false ceiling and con-
nected to ducts.
Power measurements are according to UNI EN ISO 9614-2, with unit connected to ducts and installed in the vicinity of a reflecting surface, allowing 2 dB
(A) tolerance.
Noise values referred to:
•
standard operation with air flow rate from 320mc/h to 125mc/h
•
SILET mode with air flow rate from 210mc/h to 125mc/h
•
SUPER SILET mode with air flow rate 125mc/h
SILENT and SUPER SILENT modes (setting from remote control) operate a reduction of compressor and fan speed, reducing their noise emission
Please note that noise levels may differ significantly if the unit is installed in different conditions (ex: with surrounding obstacles, walls or similar).
SOUND POWER LEVEL (DB)
OCTAVE BAND (HZ)
Sound power level
Sound pressure
level
63 125 250 500
1000
2000
4000
8000
dB(A) dB(A)
125
24 23 33 40 34 27 24 31
33 46
150
25 24 34 40 35 28 25 32
34 47
210
30 32 37 40 38 33 27 26
36 49
270
30 32 39 40 43 39 34 33
39 52
320
34 36 43 43 47 43 38 37
43 56
[m
3
/h]
SOUND LEVELS - HEATING
Sound levels are referred to unit at nominal condition when installed in false ceiling and connected to ducts. External static pressure 50 Pa.
Heating: Ambient temperature 7°C D.B./ 6°C W.B., Extracted air temperature 20°C D.B./ 13.7°C W.B.
Average sound pressure level, according to UNIEN ISO 3744, is measured at 1m distance from the unit surface, when installed in false ceiling and con-
nected to ducts.
Power measurements are according to UNI EN ISO 9614-2, with unit connected to ducts and installed in the vicinity of a reflecting surface, allowing 2 dB
(A) tolerance.
Noise values referred to:
•
standard operation with air flow rate from 320mc/h to 125mc/h
•
SILET mode with air flow rate from 210mc/h to 125mc/h
•
SUPER SILET mode with air flow rate 125mc/h
SILENT and SUPER SILENT modes (setting from remote control) operate a reduction of compressor and fan speed, reducing their noise emission
Please note that noise levels may differ significantly if the unit is installed in different conditions (ex: with surrounding obstacles, walls or similar).
Summary of Contents for ELFOFresh EVO CPAN-YIN
Page 1: ...Change living home MANUAL FOR INSTALLATION USE AND MAINTENANCE ELFOFresh EVO CPAN YIN Size2...
Page 69: ...69 12 TECHNICAL DATE ELFOAir...
Page 72: ...Filter Filter only on the intake grille ELFOFresh EVO ELFOPack ELFOFresh EVO ELFOPack...
Page 73: ...Cover the plenum openings grilles with cardboard adhesive tape etc Remove caps...
Page 74: ...74 NOTE...
Page 75: ...75 NOTE...