SYSTEM COMPONENT CONFIGURATION
The radiant zone module must be configured via thermostat depending
on the components connected to the outputs.
RADIANT ZONE MODULE - CONFIGURATION
Parameters to be modified
Channel
Parameter Value
1 P02
2 P03
......... .....
6 P07
0 = Disabled
1 = Thermoregulation 1G
2 = Thermoregulation 2 G
3 = I/O
4 = Relay control ID
5 = Thermostat Module
Configuration via thermostat:
Verify that the front selector switch of the ADDRESSES are set in position zero, otherwise addresses cannot be entered using the thermostats.
1 - switch off the module
2 - connect a HID-T2, HID-T3 or HID-TI2 thermostat to channel 6
3 - move the dip-switch placed under channel 6 connectors in position
ON
4 - switch on the module, the word OFF is displayed on the thermostat
5- configure the parameters corresponding to the used channels
6 - follow the instruction at page 51 or 52
7 - once the addressing is complete, move the dip-switch placed under channel 6 connectors in position
OFF
Channel
Parameters
Description
1
P02 = 2
Thermoregulation 2
Steps
2
P03 = 0
Disabled
3
P04 = 1
Thermoregulation 1
Step
4
P05 = 0
Disabled
5
P06 = 0
Disabled
6
P07 = 1
Thermoregulation 1
Step
1
2
3
6
HID-T3
HID-TI2
5
4
HID-T2
1
2
3
5
4
6
230V
L
N
BT1 BT2
RS 485
CH 1
CH 2
CH 3
CH 4
CH 5
CH 6
COM
ID1
ID2 COM
GND
+
-
GND
+
-
GND
+
-
GND
+
-
GND
+
-
GND
+
-
GND
+
-
G
G0
G1
G0
G2
G0
G3
G0
G4
G0
G5
G0
G6 G0
C1 NO1
G1
G2
G3
G4
G5
G6
AUX
ID1
ID2
CH5
CH6
CH4
CH3
CH2
CH1
PWR
ZONE
X 10
X 1
1
0
2
3
4
5
6
7
8
9
1
0
2
3
4
5
6
7
8
9
1
0
2
3
4
5
6
7
8
9
ADDRESS
ON
OFF
Example:
Summary of Contents for ELFOControl2
Page 1: ...Installation configuration and use manual ELFOControl2 M0CZ40B12 10 16 12 2013 ...
Page 4: ......
Page 78: ......
Page 79: ......