10 Accessories
10.1 Configurations
CCK
Configuration with double fan section for recirculation, fresh and exhaust air
CCKP
Configuration with double fan section with fresh air and THOR thermodynamic recovery
1. G4 efficiency f H10 equivalent electronic filters
2. Hot water exchanger or electric heaters
3.
Handling
exchanger
4. Hot gas reheating exchanger
5. supply fan section
6. Source side exchanger
7.
Electrical
panel
8.
Exhaust
fan
9.
Overpressure
damper
10. Thermodynamic recovery exchanger, THOR
R
Return air
FA Fresh air
S
Supply air
EX Exhaust air
10.2 Heater humidifier
Start-up
Check the water supply pressure is not higher than 3 bar.
Open the flow rate measuring device/regulator and adjust it on 50% of the value in the table.
Wait 10/15 minutes so the heater soaks and starts.
Adjust the water flow rate by choosing whether to give greater importance to comfort or containment of the water consumption.
With an EXCESSIVE flow rate, it is possible for the water to flow in the channels or overflow from the bowl.
With INSUFFICIENT flow rate there is no humidifier action.
The heater is correctly wet if a veil of water shows on the external surface (with fan still).
Maintenance
The duration in time and absence of faults require constant cleaning which periodicity depends on different factors:
concentration of dust in the air, water hardness, type of operation, etc..
When cleaning comply with the following prescriptions:
1. Close the water shut-off shutter
2. Remove the evaporating heater
3. Remove the casing panel corresponding to the humidifier
4. Remove the water distributor
5. Remove the evaporating heater
6. Was evaporating heater: the evaporating heater can be washed with water against lime deposits, but must be replaced if the deposits
are of limescale type
7. Clean the spraying pipe, found on the alveolar distributor, with metal brush and steel points for the small holes
8. Check the water connection pipe is in good conditions, without holes or cuts that may cause water to leak
9. Wash inside the tank and the various components
10. Remount the evaporating heaters. ATTENTION: The evaporating heaters have a pre-set position to respect the air and water direction,
that must be in counter-current. The incorrect position jeopardises the good operation and can cause flowing of the water downstream
11. Upon dehumidifier re-start, check operation again