Page 31
minimum limit frequency(FminH).
• When protective time is more than or equal to ten
minutes.
• When T1 is higher than or equal to Tsc+
HDIFTEMP2.
Note: HDIFTEMP2 is EEPROM setting parameter. It is 2°C
usually.
• If one of the following conditions is satisfied, not
judge protective time.
• Compressor running frequency is more than test
frequency.
• When compressor running frequency is equal to
test frequency, T4 is more than 15°C or no T4 or T4
fault.
• Change setting temperature.
• Turbo or sleep function on/off.
2) When the current is higher than the predefined safe
value, surge protection is activated, causing the
compressor to cease operations.
1.6.2 Indoor Fan Control:
1) In heating mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%,or low,
medium, high and auto.
• . Anti-cold air function
• The indoor fan is controlled by the indoor
temperature T1 and indoor unit coil temperature
T2.
Δ
TE1=0
2) Auto fan action in heating mode:
• Rise curve
• When T1-Tsc is higher than -1.5°C, fan speed
reduces to 80%;
• -When T1-Tsc is higher than 0°C, fan speed reduces
to 60%;
• -When T1-Tsc is higher than 0.5°C, fan speed
reduces to 40%;
• -When T1-Tsc is higher than 1°C, fan speed reduces
to 20%.
• Descent curve
• When T1-Tsc is lower than or equal to 0.5°C, fan
speed increases to 20%;
• -When T1-Tsc is lower than or equal to 0°C, fan
speed increases to 60%;
• -When T1-Tsc is lower than or equal to -1.5°C, fan
speed increases to 80%;
• -When T1-Tsc is lower than or equal to -3°C, fan
speed increases to 100%.
1.6.3 Outdoor Fan Control:
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are
different.
1.6.4 Defrosting mode
Case 1:
• The unit enters defrosting mode according to the
temperature value of T3 and T4 as well as the
compressor running time.
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “
” symbol is displayed.
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
• T3 rises above TCDE1.
• T3 maintained above TCDE2 for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting
mode.
1.6.5 Evaporator Coil Temperature Protection
• When the evaporator temperature exceeds a preset
protection value, the compressor ceases operation.