CAUTION:
The two phases used must each measure 120V
to Neutral. Earth Ground must be connected to Neutral at
only one point, usually at the service entry breaker panel.
ATTENTION:
Les deux phases utilisées doivent mesurer
chaque 120V à Neutre. Mise à la terre doit être connecté
au Neutre en un seul point, généralement à l’entrée
panneau de disjoncteurs de service.
CAUTION:
This is a single-phase device. DO NOT connect
all three phases of a 3-phase feed!
Use any two
phases of a three-phase wye-transformer feed. The
center-point of the three phases (usually used as Neutral)
must be grounded somewhere in the system. A Neutral
connection is not required by the EVSE. Only Line 1,
Line 2, and Ground are required, as shown in
Figure 3.
ATTENTION:
Il s’agit d’un appareil monophasé.
NE PAS
relier tous les trois phases d’une alimentation
triphasée!
Vous pouvez utiliser les deux phases d’un
triphasé en étoile transformateur alimentation. Le point
central des triphasé (généralement utilisé comme
Neutre) doit être mis à la terre quelque part dans
le système. Une connexion Neutre n’est pas exigée
par la EVSE. Seulement ligne 1, ligne 2, et Mise à la
Terre sont nécessaires, comme le montre la
Figure 3.
ATENCIÓN:
Este es un dispositivo de una sola fase. ¡No
conecte las tres fases de una alimentación trifásica!
Puede utilizar cualquiera dos fases de un transformador
trifásico de alimentación “Y”. El punto central de las tres
fases (generalmente utilizado como Neutro) debe estar
conectado a tierra en algún punto del sistema. Una
conexión Neutra no es requerida por la EVSE. Sólo la
Línea 1, Línea 2, y la Conexión a Tierra son necesarias, tal y
como se muestra en la
Figura 3.