background image

Instrukcja montażu, obsługi i konserwacji  • Klimakonwektory

Installation, use and maintenance manual  • Fan coil units

FIW

Seria /

Series

Wydanie /

Edition

Katalog /

Catalogue

Zastępuje /

Superseedes

CLM 86

FIW 12÷74

04.06

05.05

Summary of Contents for FIW Series

Page 1: ...kcja montażu obsługi i konserwacji Klimakonwektory Installation use and maintenance manual Fan coil units FIW Seria Series Wydanie Edition Katalog Catalogue Zastępuje Superseedes CLM 86 FIW 12 74 04 06 05 05 ...

Page 2: ...ome w zabudowie z wlotem od spodu 1 2 Technical characteristics The fan coil unit is a terminal unit for the treatment of room air in the summer and winter seasons The versions are IV Fitted vertical units bottom inlet IF Fitted vertical units front inlet IO Fitted horizontal units rear inlet II Fitted horizontal units bottom inlet A B C C B A Wydajność Performances 1 1 At a distance of 1 m and wi...

Page 3: ...s on the water connections a special condensation collection tub is used optional The discharge of the condensation must be properly sized and the pipes must include over their entire length an inclination that allows for proper drainage of condensation If the condensation drain flows into the sewer system it is necessary to realize a trap that prevents bad odors form entering the room Fig D Atten...

Page 4: ... unit by means of the appropriate valves and check fan coil unit for proper operation Attention The first start up of the fan coil unit must be made at maximum speed letting the fan run for 4 5 hours Repeat this operation after a long shutdown period Zdalne sterowanie Remote control Złącze Connector Fig E Fig A Fig B Fig C Fig D 2 2 Obracanie wymiennika Jeżeli montaż wymaga obrócenia wymiennika po...

Page 5: ... speed and another selector to switch the unit on and off To turn on the fan coil unit use this second selector and select the operating mode Cooling Heating the optional minimum thermostat is activated Select the fan speed maximum medium minimum At maximum speed the heating or cooling action is greater In such a case temperature regulation will be provided by a room thermostat outside the unit In...

Page 6: ...air filter This cleaning will ensure excellent performance of the unit and especially good air filtration The filter must be cleaned dry with a vaccuum cleaner or washed every 15 20 days for rooms which are not overly dusty Extracting the filter from units with bottom back air intake 1 turn 90 C the two fastening hooks located under the base of the fan coil unit Fig A 2 Extract the filter and clea...

Page 7: ...with drapes or other objects that may obstruct the air flow Ostrzeżenia Warnings Nie rozlewaj ani nie rozpylaj wody na urządzenie Do not pour or spray water on the unit Nie wkładaj przedmiotów w kratkę ochronną Do not insert objects in the protection grille Nie umieszczaj ciężkich przedmiotów ani nie stawaj na urządzeniu Do not place weights on the unit NO Legenda Legend Moduł wentylatora Fan group...

Page 8: ...emperaturę Nadmierna różnica między temperaturą w pomieszczeniu i temperaturą ustawioną w ramach sterowania automatycznego Zmniejsz różnicę temperatur Klimakonwektor nie uruchamia się Brak zasilania Sprawdź obecność napięcia Defect description Possible cause Possible solution Little air coming out of fan coil unit improper setting on control panel select correct speed filter clogged clean filter obs...