Installation manual ECO-C
Components of the ECO-C air heater
1.
Body, duct connection, heating element, electronics
section and connections for supply voltage (230 V)
and controller cabling.
2.
Grille
3.
Bottom fastening screw (3 pcs)
Installation of the ECO-C air heater
1.
Drill the necessary holes in the ceiling for cables and
fastening screws by using the stencil provided with
the unit (see stencil in Appendix 1).
2.
The minimum distance of the terminal device from the
wall is 0.5 m (see Figure 1.1). Install the terminal device
at a minimum height of 1.8 m. Ensure that children can-
not get their hands on the device.
3.
Detach the grille (2) from the body. Remove the three
fastening screws (3) and pull the grille off the body (1).
4.
Insert the bottom section duct connector into the inlet
air duct, and attach the body to the ceiling with screws
(4 pcs, max Ø 5 mm).
5.
Connect the supply cable (MMJ) through a double-pole
switch, and the control unit’s bus cable (KLMA) to the
connectors in the electronics section of the terminal
device, as shown in Figures 2.1–2.3.
6.
Ensure that the connections are correct. Place the
grille back onto the body and ensure that it is properly
attached with the fastening screws.
7.
Mark the power switch clearly.
1
2
3
N
L
ECO-C distance from wall
Min. 500 mm
Figure 1.1
Figure 1.2