30
37# AC Fault Report:
-
When set to ON, the Panel will send a Fault Report after a continuous one hour of AC Fault
condition is detected.
-
When set to OFF, the Panel will not send an AC fault report.
38# Follow-On & Call-Back Function:
-
The function is available for Digital Reporting Methods (Contact ID, Scancom or Tunstall).
-
When selected as
“Follow-On”
, after a successful reporting to the Monitoring Center, the
Panel will automatically enter the specific Follow-On mode as specified by Command (
45
).
-
When selected as
“Call-Back”
, after a successful reporting to the Monitoring Center, the
Panel will automatically hang up the line and start a 5-minute waiting period to auto answer
any incoming phone calls from the Monitoring Center.
-
When selected as
“Follow-On & Call-Back”
, after a successful reporting to the Monitoring
Center, the Panel will automatically enter specific Follow-On mode as specified by
Command (
45
). Once Follow-On Mode is terminated, the Panel will automatically start a 5-
minute waiting period to auto answer any incoming phone calls from the Monitoring Center.
39# Dialing Mode:
This function is for you to select the dialing method of your telecommunications.
Two dialing methods are available for selection: Tone, Pulse.
40# Set Access Code:
-
The Access Code is used to enter Programming Menu (locally or remotely), and the Call-
Back Function. It consists of 4 digits and has been set to (8744) as factory default.
-
To set a new Access code, enter the desired (4-digit number) in this field.
41# Auto Answer for Remote Programming:
-
The Panel can be programmed to auto answer incoming phone calls after a pre-set number
of rings have been reached. The number of rings ranges from (
01
) to (
32
) rings.
-
When set as “
None
”, the Panel will not auto-answer the call by ring count. If Remote
programming is required, you will need to call the Panel twice.
42# Guard Time Delay:
-
Guard time normal is designed for any compatible sensor except for Fall Sensor (fall
detection).
-
The Panel can be programmed to delay alarm reporting from (
00
) (instant reporting) to (
99
)
seconds.
-
During Guard Time period, a continuous series of beeps will be emitted to alert user. If a
false alarm is triggered, it can be cancelled within the Guard Time Delay.
-
The Emergency alarm cannot be cancelled after the Guard Time is elapsed.
-
If an emergency alarm is triggered by pressing the Active Button on Fall Sensor, the guard
time delay time is determined by the setting of “Guard Time Delay (Normal)” instead of the
setting of “Guard Time Delay for Fall Sensor”.
-
If an emergency alarm is triggered by Fall Sensor (fall detection), guard time will be
determined by the setting of “Guard Time Delay for Fall Sensor” instead of the setting of
“Guard Time Delay (Normal)”.
43# Periodic Test Call:
-
The Panel can be programmed to make test calls periodically from every 1 – 7 or 30 days.
Whenever programming mode is accessed, the Panel will reset the Periodic Test Call timer.
-
Whe this function is disabled, the Panel will not make periodic test calls.