11 

If the Call Recipient needs more talk time, 
s/he can press any keys except 9 on their 
phone  set  to  add  another  1-30  minutes 
(set by Command #46).  

To terminate the call, press (

9

)

 

or RESET 

BUTTON  on  SUPER  32-DT35A.  For 

(9) 

Dial  Call  Reporting

,

  the  call  can  be 

terminated  when  the  call  recipient  hangs 
up. 

During  two-way  communication,  SUPER 
32-DT35A  will  emit  two  beeps  via  the 
telephone  handset  to  alert  the  call 
recipient  the  remaining  time  of  20  &  10 
secs. 

During  two-way  voice  communication,  if 
there  is  no    DTMF  command  pressed  or 
no 

Wink 

received, 

the 

call 

will 

automatically hang-up and be recorded as 
an unsuccessful call. It will retry a max of 
4 times on each Tel. Number accordingly. 
For 

(9) 

Dial  Call  Reporting

,  no  DTMF 

command  is  required  during  speech. 
Reporting  will  be  recorded  as  successful 
upon hang-up. 

Command 31  

Ringer Enable for Incoming Calls 

 

The 

SUPER 

32-DT35A 

can 

be 

programmed  to  sound  a  ring  tone  as  an 
audio  alert  or  operate    silent  for  an  in-
coming call: 

Function Selection 

Result 

(0) 

OFF  

(Ring Tone Disable) 

(1) 

ON 

(Ring Tone Enable) 

 

Factory Default

 

is set as (

0

), 

OFF

.  

<NOTE> 

 

If  the  function  is  set  to 

ON

,  you  can 

answer  the  incoming  call  by  pressing  the 

HELP BUTTON

 or 

Pendant Button

 

The  time-out  period  for  the  incoming  call 
is  30  minutes;  during  the  communication, 
the SUPER 32-DT35A will emit two beeps 
via the telephone handset to alert the call 
recipient  the  remaining  time  of  20  &  10 
secs. 

 

Press  any  DTMF  keys  (

except  DTMF#9

can extend another 30 min. 

 

To  terminate  the  incoming  call:  (1)  press 
the reset button on SUPER 32-DT35A; or, 
(2)  press  DTMF  #9  from  the  call 
recipient’s end.  

 

 

Command 32  

Audible Fault Alert  

 

The 

SUPER 

32-DT35A 

can 

be 

programmed  to  sound  detected  and 
existent Fault Alert Beeps 

every 30 secs.

 

Function Selection 

Result 

(0) 

OFF 

(No Warning Beep) 

(1) 

ON 

(With Warning Beep)

 

 

Factory Default

 

is

 

set as (

0

), 

OFF

.  

 

The  fault  situation  includes  Low  Battery 

Fault  (for  both  SUPER  32-DT35A  and 
Devices) and AC Failure.

 

Command 33  

Help Arrived Signaling  

This function is only available for the digital 
Contact ID reporting method.  

 

It  is  used  for  the  Monitoring  Center 
personnel to confirm if the help has arrived 
for the user or not. 

 

If Help Arrived Signaling is set to 

ON

, once 

the  Alarm  Reporting  is  completed,  the 
HELP BUTTON white backlight will start to 
flash.  

Press the RESET BUTTON when the Help 
arrives,  and  SUPER  32-DT35A  will  report 
to  monitoring  center  and  the  HELP 
BUTTON white backlight will stop flashing. 

 

If  Help  Arrived  Signaling  is  set  to 

OFF

once  the  Alarm  Reporting  is  completed, 
SUPER 32-DT35A will return to idle mode.  

 

Function Selection 

Result 

(0) 

OFF

  

(disable) 

(1) 

ON

  

 

(enable) 

Summary of Contents for SUPER 32-DT35A

Page 1: ...Super 32 DT35A User Manual...

Page 2: ..._____________________ 6 5 1 Local Programming Mode under Two way communication ________________________ 6 5 2 Remote Programming Mode _____________________________________________________ 6 5 2 1 Auto...

Page 3: ...est Call ______________________________________________________________________ 47 6 6 Factory Reset__________________________________________________________________ 47 6 7 Enable Disable System Repo...

Page 4: ...distorted by the Internet phone connection 1 2 What s in the Box Your SUPER 32 DT35A package includes the following items Items SUPER 32 DT35A Panel A DC 12V 1A power adapter A Telephone Cord SUPER 32...

Page 5: ...e while in two way communication 14 Learn Button Press hold for 6 sec enter Learning Mode Press hold for 16 sec disable mobility setting 2 2 The Power Supply An AC power adapter is required to connect...

Page 6: ...located alongside other radio transmitting devices such as mobile phones cordless phone or wireless computer network Wi Fi devices Important When drilling into a wall ensure there are no hidden cable...

Page 7: ...it receives a test code from any device Learn in Devce under Local Learning Mode 1 Press and hold the Learn Button of the SUPER 32 DT35A When pressed the SUPER 32 DT35A will emit one beep sound initia...

Page 8: ...Release the Learn Button at the voice prompt Release the button Ready to learn sensor SUPER 32 DT35A is now in learning mode and the white backlight will start flashing quickly 3 Under learning mode...

Page 9: ...perator should instruct the user to enter 99 followed by to exit Programming mode and slide the Local Programming Mode Slide Switch back to Normal position NOTE The user should wait for each vocal ins...

Page 10: ...ing commands under Local Programming Mode or Remote Programming Mode Another programming option is to use the programming software Super Tool to program your SUPER 32 DT35A from your computer Please r...

Page 11: ...led calling the SUPER 32 DT35A with the 11th Caller ID will disable the system reporting function When SUPER 32 DT35A reporting function is disabled calling the Control Panel with the 11th Caller ID w...

Page 12: ...reporting sequence will go through the same reporting destination for 4 times until reporting to the next reporting destination for 4 times E g 1 1 1 1 2 2 2 2 3 Function Selection Result 0 Alternate...

Page 13: ...35A will follow the report settings for the 1st 6th Tel Numbers respectively 9 Dial Call Reporting is set as factory default for SUPER 32 DT35A Dial Call Reporting is a new reporting method used for A...

Page 14: ...ime out period for the incoming call is 30 minutes during the communication the SUPER 32 DT35A will emit two beeps via the telephone handset to alert the call recipient the remaining time of 20 10 sec...

Page 15: ...ng beeps guard time tone key tone and ring NOTE In silent mode the speaker still functions normally for two way voice communication and voice message playback Function Selection Result 0 ON Silent 1 O...

Page 16: ...hin 2 mins will cause SUPER 32 DT35A to automatically disconnect the call To terminate the call press DTMF 9 or RESET BUTTON on SUPER 32 DT35A If the 5 minute waiting period is up SUPER 32 DT35A will...

Page 17: ...ng mode is accessed SUPER 32 DT35A will reset the Periodic Test Call timer Command 44 Mobility Timer This function monitors user movement around the premises and sends an inactivity report to the Moni...

Page 18: ...for 1 10 minutes set by Command 46 that gives the user the ability to speak directly with the Monitoring Center Personnel If either Scancom or Tunstall reporting format is selected SUPER 32 DT35A will...

Page 19: ...l be sent based on your reporting methods without guard time waiting Command 53 Voice Prompt Language This command is used to set voice prompt language 0 English 1 Spanish 2 Russian 3 Arabic Factory d...

Page 20: ...l s 56 1st 2nd 3rd Tel s 123 1st 3rd 4th Tel s 134 1st 4th 6th Tel s 146 2nd 3rd 5th Tel s 235 2nd 4th 5th Tel s 245 2nd 5th 6th Tel s 256 1st 2nd 3rd 4th 5th 6th Tel s 123456 Alarm Status will be rep...

Page 21: ...Enter a telephone number followed by to program the telephone number NOTE When you program the phone number entering will cause a 3 second pause is for a switchboard system extension etc The telephone...

Page 22: ...within the signal reception range of SUPER 32 DT35A If no signal is received within 20 sec SUPER 32 DT35A will emit a long beep and automatically returns to Programming mode Step 3 SUPER 32 DT35A wil...

Page 23: ...903 for 93 Silent Device or 0904 for 94 Non silent Device Enter 0903 for learning in silent devices Enter 0904 for learning in smoke detectors CO detectors pendants fixed emergency transmitters or lon...

Page 24: ...Plug the PC Programming cable QT cable A into the Programming Telephone Jack of the panel Step 3 Connect QT cable A to the USB port on your computer See Figure 1 for connection diagram between medical...

Page 25: ...o start programming with Super Tool programming software via USB port To download Super Tool programming software open your browser and type below URL in the address bar https www climax com tw climax...

Page 26: ...port connected to the panel enter Panel Access Code Default 8744 and then click Open Step 4 A Read All command success message will pop up The current firmware version of the panel will be displayed o...

Page 27: ...A click on different function tabs to see and edit the panel functions 5 4 1 1 Report The Report tab allows the user to configure report settings Dial Call Reporting Dial Call Reporting is a new repor...

Page 28: ...ul digital reporting in CID Scancom Tunstall or Franklin 4 2 format and one successful speech reporting If only digital reporting is programmed or only speech reporting is programmed the sequence of r...

Page 29: ...n Pendant 1 is pressed or triggered under Low Battery status 04 Pendant 2 Emergency with Low Battery When Pendant 2 is pressed or triggered under Low Battery status 05 Pendant 1 Low Battery When Penda...

Page 30: ...gency Pendant WTR supervision failure status is restored 27 CO Alarm When the Carbon Monoxide Detector CO is triggered 28 CO Alarm Restore When the Carbon Monoxide Detector CO emergency status is rest...

Page 31: ...o be programmed in this tab This tab is only available when the Others radio button is selected in the Report tab 01 06 Telephone Number Programming 01 06 Used to program the 1st 6th Tel numbers respe...

Page 32: ...ignaling is set to ON once the Alarm Reporting is completed the HELP BUTTON backlight will start to flash Press the RESET BUTTON when the Help arrives and the panel will report to monitoring center an...

Page 33: ...8744 as factory default To set a new Access code enter the desired 4 digit number in this field 41 Auto Answer for Remote Programming The Panel can be programmed to auto answer incoming phone calls a...

Page 34: ...Command 46 that gives the user the ability to speak directly with the Monitoring Center Personnel If either Scancom or Tunstall reporting format is selected the Panel will ignore this field s selecti...

Page 35: ...anel will dial the telephone number programmed in this field and open two way communication when the call is answered When entering the phone number entering represent a 3 sec pause e g Switchboard sy...

Page 36: ...High Temperature Reporting threshold in degrees Fahrenheit 32 F 212 F 56 Low Temperature Reporting Set the Low Temperature Reporting threshold in degrees Fahrenheit 32 F 212 F 5 4 1 6 CO2 The CO2 tab...

Page 37: ...ces The available devices that can be learnt in via Command 93 and 94 are PIR Sensor PIR Smoke Detector SD Carbon Monoxide CO Carbon Dioxide Detector CO2 Temperature Sensor TS Fixed Panic Button PB Wr...

Page 38: ...is prohibited unless it is removed from the system first 95 Learn In Sensor with Device ID If sensor device ID is given please refer to label sticking on the device or consult the supplier you can le...

Page 39: ...e command success will pop up 81 Remove Zone 1 Device Click Remove to remove zone 1 device from the Panel A message Remove Zone 1 Device command success will pop up 82 Remove Zone 2 Device Click Remov...

Page 40: ...he Panel will instantly pick up any call that has 321 as the last 3 digits If a number string 17605851848 is programmed the Panel will instantly pick up any call that has 7605851848 as the last 10 dig...

Page 41: ...hen Default is selected the Super Tool will display default configurations of the Panel you can use this profile to return the Panel to its default setting New Profile To create a new profile click on...

Page 42: ...puter Please see pictures below as examples When you use another computer to execute the Super Tool and you wish to apply the configurations of the profiles you created on the old computer please make...

Page 43: ...40...

Page 44: ...ts The first digit 1 of the Caller ID will be ignored The 11 th Caller ID is used for disabling enabling system reporting function Please refer to 5 6 Enable Disable System Reporting 6 1 3 AC Power Ch...

Page 45: ...t reminder Inactivity timer expiring please reset at every 5 minutes to notify the user for 30 minutes When the Mobility timer is not reset after 30 minutes SUPER 32 DT35A will send a Mobility Timer E...

Page 46: ...ve Guard Time Delay and will be reported immediately SUPER 32 DT35A will play voice prompt Fire Alarm Carbon Monoxide Alarm to inform the user of the alarm at hand During this time period the Control...

Page 47: ...er 1 to LISTEN IN ONLY Enter 3 to open TWO WAY VOICE COMMUNICATION Enter 5 to HANG UP Enter to TOGGLE 3 TUNSTALL FORMAT Enter C to TALK ONLY Enter to LISTEN IN ONLY Enter 3 to open TWO WAY VOICE COMMU...

Page 48: ...t to add another 1 30 minutes set by Command 46 To terminate the call press either DTMF 9 or RESET button on SUPER 32 DT35A During the Speech period if there is no any DTMF command pressed the call wi...

Page 49: ...he learning mode To conduct Walk Test Step 3 Move the device to your desirable location in the house and press the sensor button to observe the range of its operation Step 4 If SUPER 32 DT35A responds...

Page 50: ...SUPER 32 DT35A Make sure the power cord is still plugged into the DC Jack Step 2 Press the Power Button again to power on SUPER 32 DT35A while holding down both the HELP RESET buttons until one long...

Page 51: ...re than 10 sec the Green LED flashes every 2 sec with a beep every 30 secs When AC Power for the Medication Dispenser fails and lasts for 24 hours 302 Panel Low battery When SUPER 32 DT35A is under Lo...

Page 52: ...t Transmitter Emergency Pendant WTR for a pre set period by Command 49 D 1014 Device Low Battery When devices are under Low Battery Status the Green LED flashes every 2 secs with 3 beeps every hour D...

Page 53: ...eporting 535555557 WTR Supervision Failure Restore WS Emergency Restore When the WTR supervision failure status is restored When WS emergency status is restored 555555558 Device Low Battery When devic...

Page 54: ...S is restored 88 Periodic Test Report AKA Self test report Global test When the SUPER 32 DT35A reports Periodic test call to monitoring Center When the SUPER 32 DT35A reports Global Test to Monitoring...

Page 55: ...triggered When Smoke Detector SD button is pressed 08 Fall emergency When the Fall Sensor button is presssed 09 Panel AC Failure When the Panel AC power failure is detected and lasts for more than on...

Page 56: ...35A is unable to receive the signal transmitted from the Wrist Transmitter Emergency Pendant WTR for a pre set period by Command 4 26 WTR Supervision Restore When the Wrist Transmitter Emergency Penda...

Page 57: ...status 42 Water Sensor Low Battery Restore When the water sensor battery is back to normal 43 Medication Dispenser Mechanism Jam When the Medication Dispenser is jammed e g White T Bar not in the cor...

Page 58: ...nce 0 Alternate Reporting Sequence 1 One by One Reporting Sequence Bi Alternate Reporting Sequence 10 Bi Global Account Number 4 to 12 digits Bi No account number 11 Bi 4 12 digits Account number 4 Te...

Page 59: ...Call Reporting 24 Bi To Set Reporting Method for Tel Number 4 0 Contact ID 1 Scancom 2 Tunstall 3 Speech 4 VRI 6 Franklin 4 2 8 Auto CID Franklin 4 2 9 Dial Call Reporting Note When any of the comman...

Page 60: ...2mins 03 3mins 04 4mins 05 5mins 06 6mins 07 7mins 08 8mins 09 9mins 10 10mins Bi 2 minutes 47 Bi Off set time 1 1 hour 2 2 hours 3 3 hours 4 4 hours 5 8hours 6 12 hours Bi 1 Hour 49 Bi Supervision 0...

Page 61: ...device ID Enter Device Type 93 or 94 Device ID Input rule For single digit number enter 0 followed by the number Enter 01 instead of 1 0 9 00 09 A 10 B 11 C 12 D 13 E 14 F 15 Example Device Type 93 De...

Page 62: ...sensor has been learnt into the Control Panel Power on Played when the Panel is powered on Calling the Care Center Played once after pressing the Help Button on the Control Panel Active Button on Pan...

Reviews: