background image

8X8A Relay Module 

(CL-DR-RL8X8A-N)

Rail Mounting

8X8A Relay Module is designed to be installed on a standard 
35 mm wide DIN rail (EN 50022, BS 5584). 

Hook the module from the top, pull down the rail moun ng 
clips,  push  the  module  to  the  rail  and  release  the  rail 
moun ng clips.

Screw Mounting

Screw  the  module  to  any  surface  through  4  corner  screw 
holes.

3

4

1

2

INSTALLATION GUIDE 

 version 1.0.1

Input Voltage

18V-24V DC (24V DC is recommended)

Input Current

170mA (for 24V DC)

I/O Connec ons

C-Bus

2 X RJ45

Output

8 X relay channel -8A per Channel

(rising-cage 5mm screw terminals)

Pr

oduct Specific

aon

1. Screw holes
2. Output connectors
3.Rail moun ng clips
4. Channel LEDs
5. Status LEDs
6. Control bu ons (1-8)
7. RS-485 jack

CL-DR-RL8X8A-N

C-Bus

C-Bus

Power In: 24V DC, 170mA max, from data bus

1

2

3

1

1
4

1
5
7

6

3
7

#2

#3

#4

#5

#8

#1

#6

#7

C-Bus

C-Bus

#2

#3

#4

#5

#8

#1

#6

#7

Compatible with Control4

CL-DR-RL8X8A-N

C-Bus

C-Bus

Power In: 24V DC, 170mA max, from data bus

1

2

3

Change Module Address

In order to change   the module address follow steps below consecu vely and uninterruptedly:
1.
 Disconnect the main power. Hold bu on #1 & #2 simultaneously (bu on’s and LED’s number 
sequence is considered from right to le as shown in following picture)

 

2. Reconnect the main power. Release bu on #2 a er LEDs #1 to #4 flashed. Then release bu on #1 
a er LEDs #1 and #2 flashed. Power LED will start flashing quickly.
3. Press bu on #1, 4  mes. Then the module address will be displayed by LEDs in binary. 
4. Press bu on #1 to increase the module address and bu on #2 to decrease it.
5. Press bu on #3 to save the module address and bu on #4 to cancel. A er saving the new module 
address or canceling the process, the module will reset.

The  devices  which  are  connected  from  a  common  interface  cannot  have  same  module 

address.